Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 88
Table 30 Liebert Mini-Mate2
8 Ton - Input and Holding - L8T
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Temperature 40001 1
Humidity 40002 1
Cooling 40003 1 1=On / 0=Off
Heating 40004 1 1=On / 0=Off
Humidification 40005 1 1=On / 0=Off
De-humidification 40006 1 1=On / 0=Off
Econ-O-Cycle 40007 1 1=On / 0=Off
Stages 40008 1
% Capacity 40009 1
Analog input 1 40023 1
A/D raw value w/ slope =1
and offset = 0
Analog input 2 40024 1
A/D raw value w/ slope =1
and offset = 0
Analog input 3 40025 1
A/D raw value w/ slope =1
and offset = 0
Analog input 4 40026 1
A/D raw value w/ slope =1
and offset = 0
Alarm Points
Communications 40289 1 Bit 0
Local Off 40289 1 Bit 1
Remote Off 40289 1 Bit 2
High Head Pressure 1 40289 1 Bit 3
High Head Pressure 2 40289 1 Bit 4
Loss of Airflow 40289 1 Bit 5
Standby Glycol Unit On 40289 1 Bit 6
Not Used 40289 1 Bit 7
Change Filters 40289 1 Bit 8
High Temperature 40289 1 Bit 9
Low Temperature 40289 1 Bit 10
High Humidity 40290 1 Bit 0
Low Humidity 40290 1 Bit 1
Humidifier Problem 40290 1 Bit 2
Smoke Detected 40290 1 Bit 8
Loss of Water 40290 1 Bit 9
Standby Unit On 40290 1 Bit 10
Not Used 40291 1 Bit 0
Short Cycle 40291 1 Bit 1
Loss of Power 40291 1 Bit 2
Local Alarm 1 40291 1 Bit 6
Local Alarm 2 40291 1 Bit 7