Modbus 485 and Modbus IP Protocols - UPS Systems
173 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
DC Bus
DC Bus Voltage 30465 — 1 —
Units : VDC
Uint16
DC Bus Current 30466 — 1 —
Units : A DC
Int16
DC Bus Qualification Status 30467 — 1 —
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Output
System Output Voltage RMS A-B 30478 — 1 10
Units : VAC
Uint16
System Output Voltage RMS B-C 30479 — 1 10
Units : VAC
Uint16
System Output Voltage RMS C-A 30480 — 1 10
Units : VAC
Uint16
System Output Voltage RMS A-N 30481 — 1 10
Units : VAC
Uint16
System Output Voltage RMS B-N 30482 — 1 10
Units : VAC
Uint16
System Output Voltage RMS C-N 30483 — 1 10
Units : VAC
Uint16
System Output RMS Current Phs A 30484 — 1 —
Units : A AC
Uint16
System Output RMS Current Phs B 30485 — 1 —
Units : A AC
Uint16
System Output RMS Current Phs C 30486 — 1 —
Units : A AC
Uint16
System Output Frequency 30487 — 1 100
Units : Hz
Uint16
System Output Power 30488 — 1 —
Units : kW
Uint16
System Output Apparent Power 30489 — 1 —
Units : kVA
Uint16
System Output Power Factor Phs A 30490 — 1 100 Uint16
System Output Power Factor Phs B 30491 — 1 100 Uint16
System Output Power Factor Phs C 30492 — 1 100 Uint16
System Output Pct Power Phase A 30493 — 1 —
Units : %
Uint16
System Output Pct Power Phase B 30494 — 1 —
Units : %
Uint16
System Output Pct Power Phase C 30495 — 1 —
Units : %
Uint16
System Output Pct Pwr (VA) Phs A 30496 — 1 —
Units : %
Uint16
System Output Pct Pwr (VA) Phs B 30497 — 1 —
Units : %
Uint16
System Output Pct Pwr (VA) Phs C 30498 — 1 —
Units : %
Uint16
Output Qualification Status 30499 — 1 —
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label
Input Holding # of Reg Scale Notes/Units