Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - UPS Systems
321 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 107 Liebert NXL
- 60Hz, UL version (Model 40) - Analog Data
Data Label
Object Type Instance
Object
Name Access Notes
Liebert
NXL Type
Input
System Input RMS A-B Analog_Value 1 4097_1 RD Units: VAC
SMS, 1+N,
N+1
System Input RMS B-C Analog_Value 2 4099_1 RD Units: VAC
SMS, 1+N,
N+1
System Input RMS C-A Analog_Value 3 4101_1 RD Units: VAC
SMS, 1+N,
N+1
System Input RMS Current Phase A Analog_Value 4 4113_1 RD Units: A AC
SMS, 1+N,
N+1
System Input RMS Current Phase B Analog_Value 5 4114_1 RD Units: A AC
SMS, 1+N,
N+1
System Input RMS Current Phase C Analog_Value 6 4115_1 RD Units: A AC
SMS, 1+N,
N+1
System Input Frequency Analog_Value 7 4105_1 RD Units: Hz SMS, 1+N,
Bypass
Bypass Input Voltage RMS A-B Analog_Value 18 4125_1 RD Units: VAC
SMS, 1+N,
SCC
Bypass Input Voltage RMS B-C Analog_Value 19 4126_1 RD Units: VAC
SMS, 1+N,
SCC
Bypass Input Voltage RMS C-A Analog_Value 20 4127_1 RD Units: VAC
SMS, 1+N,
SCC
Bypass Input Frequency Analog_Value 21 4131_1 RD Units: Hz
SMS, 1+N,
SCC
Bypass Sync Phase Difference Analog_Value 22 4136_1 RD Units: deg
SMS, 1+N,
SCC
Bypass SS Overload Time Remain Analog_Value 23 4157_1 RD Units: sec
SMS, 1+N,
SCC
Auto Retransfer Time Remaining Analog_Value 24 4738_1 RD Units: sec
SMS, 1+N,
SCC
Battery
Battery Total Discharge Time Analog_Value 35 4152_1 RD Units: hr
SMS, 1+N,
N+1
Battery Percentage Charge Analog_Value 36 4153_1 RD
SMS, 1+N,
N+1
Battery Volts at Main Disconnect Analog_Value 37 4154_1 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 1 Analog_Value 38 4155_1_1 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 2 Analog_Value 39 4155_1_2 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 3 Analog_Value 40 4155_1_3 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 4 Analog_Value 41 4155_1_4 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 5 Analog_Value 42 4155_1_5 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 6 Analog_Value 43 4155_1_6 RD Units: VDC
SMS, 1+N,
N+1
Battery Volts for Cabinet 7 Analog_Value 44 4155_1_7 RD Units: VDC
SMS, 1+N,
N+1