Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
105 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Panel 2 Position 2
Breaker position 31607 — 1 — —
Branch Current Phase 1 31608 — 1 10 A AC
Branch Current Phase 2 31609 — 1 10 A AC
Branch Current Phase 3 31610 — 1 10 A AC
Branch Output Power (kW) 31611 — 1 1000 kW
Output kW-Hrs 31612 — 2 1000 kWH
Branch Output Power Factor 31614 — 1 100 —
Branch Output Percent Load 31615 — 1 — %
Panel 2 Position 84
Breaker position 32591 — 1 — —
Branch Current Phase 1 32592 — 1 10 A AC
Branch Current Phase 2 32593 — 1 10 A AC
Branch Current Phase 3 32594 — 1 10 A AC
Branch Output Power (kW) 32595 — 1 1000 kW
Output kW-Hrs 32596 — 2 1000 kWH
Branch Output Power Factor 32598 — 1 100 —
Branch Output Percent Load 32599 — 1 — %
Panel 3 Position 1
Breaker position 32603 — 1 — —
Branch Current Phase 1 32604 — 1 10 A AC
Branch Current Phase 2 32605 — 1 10 A AC
Branch Current Phase 3 32606 — 1 10 A AC
Branch Output Power (kW) 32607 — 1 1000 kW
Output kW-Hrs 32608 — 2 1000 kWH
Branch Output Power Factor 32610 — 1 100 —
Branch Output Percent Load 32611 — 1 — %
Panel 3 Position 2
Breaker position 32615 — 1 — —
Branch Current Phase 1 32616 — 1 10 A AC
Branch Current Phase 2 32617 — 1 10 A AC
Branch Current Phase 3 32618 — 1 10 A AC
Branch Output Power (kW) 32619 — 1 1000 kW
Output kW-Hrs 32620 — 2 1000 kWH
Branch Output Power Factor 32622 — 1 100 —
Branch Output Percent Load 32623 — 1 — %
Table 36 Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units