Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 146
Output
Source — 40050 1 —
1 = Other
2 = None
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Frequency — 40051 1 10 Units: Hz
Number Lines — 40052 1 — —
Voltage L1 — 40053 1 — Units: V
Voltage L2 — 40054 1 — Units: V
Voltage L3 — 40055 1 — Units: V
Current L1 — 40056 1 10 Units: A
Current L2 — 40057 1 10 Units: A
Current L3 — 40058 1 10 Units: A
Real Power L1 — 40059 1 10 Units: kW
Real Power L2 — 40060 1 10 Units: kW
Real Power L3 — 40061 1 10 Units: kW
Percent Load L1 — 40062 1 — Units: %
Percent Load L2 — 40063 1 — Units: %
Percent Load L3 — 40064 1 — Units: %
Bypass
Line Bads — 40070 1 — —
Frequency — 40071 1 10 Units: Hz
Number Lines — 40072 1 — —
Voltage L1 — 40073 1 — Units: V
Voltage L2 — 40074 1 — Units: V
Voltage L3 — 40075 1 — Units: V
Current L1 — 40076 1 10 Units: A
Current L2 — 40077 1 10 Units: A
Current L3 — 40078 1 10 Units: A
Alarms
Alarms Present — 40087 1 — Bit 0
On Battery — 40087 1 — Bit 2
Low Battery — 40087 1 — Bit 3
Depleted Battery — 40087 1 — Bit 4
Temperature Bad — 40087 1 — Bit 5
Input Bad — 40087 1 — Bit 6
Output Overload — 40088 1 — Bit 0
On Bypass — 40088 1 — Bit 1
Bypass Bad — 40088 1 — Bit 2
Charger Failed — 40088 1 — Bit 5
Fan Failure — 40089 1 — Bit 0
General Fault — 40089 1 — Bit 2
Table 54 Liebert NX 225-600kVA UPS - Input and Holding
3
(continued)
Data Description
Input
Holding
Register
# of
Reg Scale Notes/Units