Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 222
Free Cooling / Chilled Water
Free Cooling Valve Hours Exceeded Binary_Value 117 5306_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Free Cooling Lockout Binary_Value 118 5361_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Free Cooling Temp Sensor Issue Binary_Value 119 5362_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Reheat
Hot Water / Hot Gas Valve Hours
Exceeded
Binary_Value 130 5365_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Reheater Over Temperature Binary_Value 131 5068_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Reheat Lockout Binary_Value 132 5070_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Reheat - Electric Reheater 1
Electric Reheater Hours Exceeded Binary_Value 143 5368_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Reheat - Electric Reheater 2
Electric Reheater Hours Exceeded Binary_Value 154 5368_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Reheat - Electric Reheater 3
Electric Reheater Hours Exceeded Binary_Value 165 5368_1_3 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier
Humidifier Hours Exceeded Binary_Value 176 5037_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Humidifier Lockout Binary_Value 177 5044_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier Control Board Not Detected Binary_Value 178 5045_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier Cylinder Worn Binary_Value 179 5042_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier Issue Binary_Value 180 5043_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier Low Water Binary_Value 181 5041_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier Over Current Binary_Value 182 5040_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Humidifier Under Current Binary_Value 183 5039_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Dehumidifier
Dehumidifier Hours Exceeded Binary_Value 194 5038_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Fan
Fan Hours Exceeded Binary_Value 205 5054_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Main Fan Overload Binary_Value 206 5376_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Fan Issue Binary_Value 207 4729_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Table 76 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes