Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 100
Table 36 Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Input and Holding
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Input Power 1
Input Voltage A-B 30385 — 1 — VAC
Input Voltage B-C 30386 — 1 — VAC
Input Voltage C-A 30387 — 1 — VAC
Input Power 2
Input Voltage A-B 30391 — 1 — VAC
Input Voltage B-C 30392 — 1 — VAC
Input Voltage C-A 30393 — 1 — VAC
Output Power 1 ——
Output Voltage X-Y 30397 — 1 — VAC
Output Voltage Y-Z 30398 — 1 — VAC
Output Voltage Z-X 30399 — 1 — VAC
Output Voltage Vx 30400 — 1 — VAC
Output Voltage Vy 30401 — 1 — VAC
Output Voltage Vz 30402 — 1 — VAC
Output Current Ix 30403 — 1 — A AC
Output Current Iy 30404 — 1 — A AC
Output Current Iz 30405 — 1 — A AC
Output Neutral Current 30406 — 1 — A AC
Ground Current 30407 — 1 10 A AC
Output Frequency 30408 — 1 — Hz
Output Power (kVA) 30409 — 1 — kVA
Output Power (kW) 30410 — 1 — kW
Output kW-Hrs 30411 40411 2 — kWH
Output Power Factor 30413 — 1 100 —
Output Percent Load 30414 — 1 — %
Output Voltage Vx THD 30415 — 1 10 % THD
Output Voltage Vy THD 30416 — 1 10 % THD
Output Voltage Vz THD 30417 — 1 10 % THD
Output Current Ix THD 30418 — 1 10 % THD
Output Current Iy THD 30419 — 1 10 % THD
Output Current Iz THD 30420 — 1 10 % THD
Output Current Ix K-Factor 30421 — 1 10 —
Output Current Iy K-Factor 30422 — 1 10 —
Output Current Iz K-Factor 30423 — 1 10 —
Output Current Ix Crest Factor 30424 — 1 10 —
Output Current Iy Crest Factor 30425 — 1 10 —
Output Current Iz Crest Factor 30426 — 1 10 —