Modbus 485 and Modbus IP Protocols - UPS Systems
151 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 56 Liebert NXL
™
- 60Hz, UL version (Model 40) - Input and Holding
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types
System Date and Time 30005 — 2 —
Masks:
Year 0xFFFF 0000
Mon 0x0000 FF00
Day 0x0000 00FF
SCC, N+1,
1+N, 1+1,
SMS
System Date and Time 30007 — 2 —
Masks:
Hour 0xFF00 0000
Min 0x00FF 0000
Sec 0x0000 FF00
SCC, N+1,
1+N, 1+1,
SMS
Output Apparent Power Rating 30021 — 2 — kVA
SCC, N+1,
1+N, 1+1, SMS
System Input Nominal Voltage 30027 — 1 — VAC
SCC, N+1,
1+N, 1+1, SMS
System Output Nominal Voltage 30028 — 1 — VAC
SCC, N+1,
1+N, 1+1,
SMS
Bypass Nominal Voltage 30029 — 1 — VAC
SCC, 1+N,
1+1, SMS
System Input Nominal Frequency 30031 — 1 10 Hz
SCC, N+1,
1+N, 1+1, SMS
System Output Nominal Frequency 30032 — 1 10 Hz
SCC, N+1,
1+N, 1+1,
SMS
System Output Apparent Power 30102 — 2 — kVA
N+1, 1+N,
1+1, SMS
System Output Power 30104 — 2 — kW
N+1, 1+N,
1+1, SMS
System Input Frequency 30107 — 1 10 Hz
N+1, 1+N,
1+1, SMS
System Output Frequency 30108 — 1 10 Hz
N+1, 1+N,
1+1, SMS
Bypass Input Frequency 30109 — 1 10 Hz
SCC, 1+N,
1+1, SMS
Battery Volts at Main Disconnect 30113 — 1 — VDC
N+1, 1+N,
1+1, SMS
Battery Time Remaining 30115 — 1 — min
N+1, 1+N,
1+1, SMS
Battery Percentage Charge 30116 — 1 —
N+1, 1+N,
1+1, SMS
Inlet Air Temperature 30119 — 1 — deg C
SCC, N+1,
1+N,
1+1, SMS
System Input RMS A-B 30151 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase A 30154 — 1 — A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS A-B 30157 — 1 — VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS A-B 30161 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS A-N 30162 — 1 — VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs A 30164 — 1 — A AC
N+1, 1+N,
1+1, SMS