Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 120
Table 41 Liebert APM
, Liebert NXC
, Liebert NXR
- Input and Holding
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Input
System Input RMS A-B 30385 1 VAC
System Input RMS B-C 30386 1 VAC
System Input RMS C-A 30387 1 VAC
System Input RMS Current Phase A 30388 1 A AC
System Input RMS Current Phase B 30389 1 A AC
System Input RMS Current Phase C 30390 1 A AC
System Input Frequency 30391 1 10 Hz
System Input RMS A-N 30392 1 VAC
System Input RMS B-N 30393 1 VAC
System Input RMS C-N 30394 1 VAC
System Input Power Factor Phs A 30395 1 100
System Input Power Factor Phs B 30396 1 100
System Input Power Factor Phs C 30397 1 100
Bypass
Bypass Input Voltage RMS A-N 30401 1 VAC
Bypass Input Voltage RMS B-N 30402 1 VAC
Bypass Input Voltage RMS C-N 30403 1 VAC
Bypass Input Frequency 30404 1 10 Hz
Battery
Battery Time Remaining 30408 1 min
Battery Volts for Cabinet 30409 1 VDC
Battery Temperature for Cabinet 30410 1 deg C
Battery Temperature for Cabinet 30411 1 deg F
Inlet Air Temperature 30412 1 deg C
Inlet Air Temperature 30413 1 deg F
DC Bus Current 30414 1 A DC
UPS battery1 status 30415 1
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Output
System Output Voltage RMS A-N 30419 1 VAC
System Output Voltage RMS B-N 30420 1 VAC
System Output Voltage RMS C-N 30421 1 VAC
System Output RMS Current Phs A 30422 1 A AC
System Output RMS Current Phs B 30423 1 A AC
System Output RMS Current Phs C 30424 1 A AC
System Output Frequency 30425 1 10 Hz
System Output Voltage RMS A-B 30426 1 VAC
System Output Voltage RMS B-C 30427 1 VAC
System Output Voltage RMS C-A 30428 1 VAC
System Output Power Factor Phs A 30429 1 100
System Output Power Factor Phs B 30430 1 100