Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
161 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
MMS Module Total kVA Output 30651 1 Units : kVA SCC
MMS Module DC Bus Voltage 30652 1 Units : VDC SCC
MMS Module Battery Current 30653 1 Units : A DC SCC
MMS Module Battery Time
Remaining
30654 1 Units : min SCC
Intelligent Paralleling
Intelligent Parallel Operation
State
30658 1
0 = disabled
1 = enabled
N+1, 1+N,
SCC
Intelligent Parallel Mode 30659 1
1 = Disconnect
(More Efficient)
N+1,
1+N,
SCC
Intelligent Paralleling Shutdown
Delay
30660 1 Units : min
N+1, 1+N,
SCC
Intelligent Parallel Minimum
Redundancy
30661 1
N+1, 1+N,
SCC
Intelligent Parallel Maximum
Time in Standby
30662 1 Units : day
N+1, 1+N,
SCC
ECO Mode
ECO Mode Operation State 30666 40666 1
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Continuous Operation - ECO Mode 30667 1
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Maximum Auto Suspensions - ECO
Mode
30668 1
SMS, 1+N,
SCC
Restart Delay - ECO Mode 30669 1 Units : min
SMS, 1+N,
SCC
Time Remaining - ECO Mode 30670 1 Units : min
SMS, 1+N,
SCC
EcoModeSchedule 1
Schedule Operation State - ECO
Mode
30674 1
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode 30675 1
0 = stop
1 = start
SMS, 1+N,
SCC
Schedule Day of Week - ECO
Mode
30676 1
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
SMS, 1+N,
SCC
Schedule Hour - ECO Mode 30677 1 Units : hr
SMS, 1+N,
SCC
Schedule Minute - ECO Mode 30678 1 Units : min
SMS, 1+N,
SCC
Table 56 Liebert NXL
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL