Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
231 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Humidifier
Humidifier Hours Analog_Value 186 5369_1 RW Units: hr
1, 2, 3,
4, 5, 6
Humidifier Hours Threshold Analog_Value 187 5370_1 RW Units: hr
1, 2, 3,
4, 5, 6
Infrared Humidifier Flush Rate Analog_Value 188 5445_1 RW Units: %
1, 2, 3,
4, 5, 6
Dehumidifier
Dehumidifier Hours Analog_Value 199 5371_1 RW Units: hr
1, 2, 3,
4, 5, 6
Dehumidifier Hours Threshold Analog_Value 200 5372_1 RW Units: hr
1, 2, 3,
4, 5, 6
Fan
Fan Speed Maximum Set Point Analog_Value 211 5050_1 RW Units: %
1, 2, 3,
4, 5, 6
Fan Hours Analog_Value 212 5374_1 RW Units: hr
1, 2, 3,
4, 5, 6
Fan Hours Threshold Analog_Value 213 5375_1 RW Units: hr
1, 2, 3,
4, 5, 6
Fan Speed Minimum Set Point Analog_Value 214 5051_1 RW Units: %
2, 3, 4,
5, 6
Fan Speed Temperature Set
Point
Analog_Value 215 5585_1 RW Units: deg C
2, 3, 4,
5, 6
Fan Speed Temperature Set
Point
Analog_Value 10215 5585_1_deg_F RW Units: deg F
2, 3, 4,
5, 6
Analog Inputs 1
Analog Input Reading Analog_Value 224 5378_1 RD
1, 2, 3,
4, 5, 6
Analog Inputs 2
Analog Input Reading Analog_Value 235 5378_2 RD
1, 2, 3,
4, 5, 6
Analog Inputs 4
Analog Input Reading Analog_Value 257 5378_4 RD
1, 2, 3,
4, 5, 6
System Info
BMS Timeout Period Analog_Value 268 5075_1 RW Units: min
1, 2, 3,
4, 5, 6
Auto Restart Delay Analog_Value 269 4710_1 RW Units: sec
1, 2, 3,
4, 5, 6
Standby Units Analog_Value 270 5314_1 RW
2, 3, 4,
5, 6
System Operations
Fan Speed Analog_Value 280 5077_1 RD Units: %
1, 2, 3,
4, 5, 6
Compressor Utilization Analog_Value 281 5078_1 RD Units: % 1
Free Cooling Valve Open
Position
Analog_Value 282 5379_1 RD Units: %
1, 2, 3,
4, 5, 6
Maintenance Ramp Analog_Value 283 4870_1 RD Units: %
1, 2, 3,
4, 5, 6
Table 78 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes