Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 178
Module Output Breaker for Module 3 30646 — 1 —
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 4 30647 — 1 —
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 5 30648 — 1 —
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 6 30649 — 1 —
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 7 30650 — 1 —
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 8 30651 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 1 30652 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 2 30653 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 3 30654 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 4 30655 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 5 30656 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 6 30657 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 7 30658 — 1 —
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 8 30659 — 1 —
0 = Open
1 = Close
2 = Not Installed
System Output Breaker 30660 — 1 —
0 = Open
1 = Close
2 = Not Installed
System Load Bank Breaker 30661 — 1 —
0 = Open
1 = Close
2 = Not Installed
System Isolation Output Breaker 30662 — 1 —
0 = Open
1 = Close
2 = Not Installed
SCC Event Summary 30663 — 1 —
0 = None
1 = Alarm
2 = Fault
Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding
Data Label
Input Holding # of Reg Scale Notes/Units