Modbus/BACnet IP 290
Table 95 Liebert XDP
, Liebert XDC
- Glossary
Data Label Data Description
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is
restored before restarting the unit.
Calculated Next Maintenance Month
Calculated month of the next scheduled maintenance. Used in conjunction
with [Calculated Next Maintenance Year].
Calculated Next Maintenance Year
Calculated year of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Month].
Chilled Water Cntrl Valve Pos - Event
Control
Enable/disable the activation of the [Chilled Water Control Valve Position]
event. If set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Chilled Water Cntrl Valve Pos - Event Type The event type for the [Chilled Water Control Valve Position] event.
Chilled Water Control Valve Position
Chilled water valve out of position. Chilled water control valve position does
not match expected value.
Circuit 1 Low Suction Pressure - Event
Control
Enable/disable the activation of the [Circuit 1 Low Suction Pressure] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Circuit 1 Low Suction Pressure - Event
Type
The event type for the [Circuit 1 Low Suction Pressure] event.
Circuit 1 Low Suction Pressure Compressor circuit 1 low suction pressure.
Circuit 2 Low Suction Pressure - Event
Control
Enable/disable the activation of the [Circuit 2 Low Suction Pressure] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Circuit 2 Low Suction Pressure - Event
Type
The event type for the [Circuit 2 Low Suction Pressure] event.
Circuit 2 Low Suction Pressure Compressor circuit 2 low suction pressure.
Cold Aisle Over Temp Threshold Upper threshold value used in the [Cold Aisle Temp Out of Range] event.
Cold Aisle Temp Out of Range
The air temperature in the cold aisle is either above [Cold Aisle Over Temp
Threshold] or below [Cold Aisle Under Temp Threshold].
Cold Aisle Under Temp Threshold Lower threshold value used in the [Cold Aisle Temp Out of Range] event.
Communication Status Communication status of remote device.
Compressor 1A High Head Pressure -
Event Control
Enable/disable the activation of the [Compressor 1A High Head Pressure]
event. If set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Compressor 1A High Head Pressure -
Event Type
The event type for the [Compressor 1A High Head Pressure] event.
Compressor 1A High Head Pressure Compressor 1A high head pressure.
Compressor 1A Short Cycle - Event
Control
Enable/disable the activation of the [Compressor 1A Short Cycle] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Compressor 1A Short Cycle - Event Type The event type for the [Compressor 1A Short Cycle] event.
Compressor 1A Short Cycle
Compressor 1A short cycle. A short cycle is defined as turning on and off a
number of times over a set time period.
Compressor 1A State Compressor 1A operational state.
Compressor 1B High Head Pressure -
Event Control
Enable/disable the activation of the [Compressor 1B High Head Pressure]
event. If set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Compressor 1B High Head Pressure -
Event Type
The event type for the [Compressor 1B High Head Pressure] event.
Compressor 1B High Head Pressure Compressor 1B high head pressure.
Compressor 1B Short Cycle - Event
Control
Enable/disable the activation of the [Compressor 1B Short Cycle] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.