Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 86
Table 29 Liebert DataMate
, Liebert Mini-Mate2
- Input and Holding - MM2
Controller MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Temperature 40001 1
Humidity 40002 1
Cooling 40003 1 1=On / 0=Off
Heating 40004 1 1=On / 0=Off
Humidification 40005 1 1=On / 0=Off
Dehumidification 40006 1 1=On / 0=Off
Econ-o-Cycle 40007 1 1=On / 0=Off
Stages 40008 1
% Capacity 40009 1
Alarm Points
Communications 40289 1 Bit 0
Local Off 40289 1 Bit 1
Remote Off 40289 1 Bit 2
High Head Pressure 1 40289 1 Bit 3
Loss of Airflow 40289 1 Bit 5
Standby Glycol Unit On 40289 1 Bit 6
Change Filters 40289 1 Bit 8
High Temperature 40289 1 Bit 9
Low Temperature 40289 1 Bit 10
High Humidity 40290 1 Bit 0
Low Humidity 40290 1 Bit 1
Humidifier Problem 40290 1 Bit 2
Smoke Detected 40290 1 Bit 8
Loss of Water Flow 40290 1 Bit 9
Standby Unit On 40290 1 Bit 10
Short Cycle 40291 1 Bit 1
Loss of Power 40291 1 Bit 2
Local Alarm 1 40291 1 Bit 6
Local Alarm 2 40291 1 Bit 7
Local Alarm 3 40291 1 Bit 9
Local Alarm 4 40291 1 Bit 10
Run Hours (View)
Compressor 1 40019 1
Fan Motor 40020 1
Humidifier 40021 1