Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 204
Output Undervoltage 40290 1 Bit 7
Output Waveform Error 40290 1 Bit 8
Transfer Count Block 40290 1 Bit 9
Overload Shutdown 40290 1 Bit 10
Overtemperature Shutdown 40291 1 Bit 0
Emergency Stop 40291 1 Bit 1
Overload Present 40291 1 Bit 2
Overload Shutdown TO 40291 1 Bit 3
Display Error 40291 1 Bit 4
Display Error 40291 1 Bit 5
Invewrter Over Capacity 40291 1 Bit 6
Parallel Bus Open 40291 1 Bit 7
Battery Ground Fault 40291 1 Bit 8
Bypass Backfeed 40291 1 Bit 9
Bypass Sync Inhibited 40291 1 Bit 10
Bypass ECO Mode 40291 1 Bit 11
Fan Failure 40291 1 Bit 12
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 72 Liebert SICE 7200
- Input and Holding - SSC (continued)
Controller System Control Cabinet - SSC
Liebert Products Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units