Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 264
Ext Reheat Lockout - Event Type MultiState_Value 191 5085_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Humidifier Lockout - Event Control MultiState_Value 192 5086_1 RW
1 = disabled
2 = enabled
Ext Humidifier Lockout - Event Type MultiState_Value 193 5087_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Compressor Lockout - Event Control MultiState_Value 194 5088_1 RW
1 = disabled
2 = enabled
Ext Compressor Lockout - Event Type MultiState_Value 195 5089_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Over Temperature - Event Control MultiState_Value 196 5090_1 RW
1 = disabled
2 = enabled
Ext Over Temperature - Event Type MultiState_Value 197 5091_1 RW
1 = Message
2 = Warning
3 = Alarm
Condenser VFD Issue - Event Control MultiState_Value 198 5092_1 RW
1 = disabled
2 = enabled
Condenser VFD Issue - Event Type MultiState_Value 199 5093_1 RW
1 = Message
2 = Warning
3 = Alarm
Condenser TVSS Issue - Event Control MultiState_Value 200 5094_1 RW
1 = disabled
2 = enabled
Condenser TVSS Issue - Event Type MultiState_Value 201 5095_1 RW
1 = Message
2 = Warning
3 = Alarm
Condenser 1 Issue - Event Control MultiState_Value 202 5096_1 RW
1 = disabled
2 = enabled
Condenser 1 Issue - Event Type MultiState_Value 203 5097_1 RW
1 = Message
2 = Warning
3 = Alarm
GlobalCondenser
Condenser Refrigerant Type MultiState_Value 215 5533_1 RD
1 = R22
2 = R407C
3 = R410A
GlobalCondenser - LowNoiseMode
Condenser Low Noise Mode State MultiState_Value 227 5546_1_1 RD
1 = Inactive
2 = Active (Interval)
3 = Active (Full Day)
Condenser Low Noise Mode Schedule
Control
MultiState_Value 228 5547_1_1 RW
1 = disabled
2 = enable
Table 85 Liebert CRV
- Multistate Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes