Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 160
MMS Module Output Voltage
Status
30557 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
1+N, SCC
MMS Module Output Source 30558 1
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
1+N, SCC
MMS Module Total kW Output 30559 1 Units : kW SCC
MMS Module Total kVA Output 30560 1 Units : kVA SCC
MMS Module DC Bus Voltage 30561 1 Units : VDC SCC
MMS Module Battery Current 30562 1 Units : A DC SCC
MMS Module Battery Time
Remaining
30563 1 Units : min SCC
ModuleList 2
MMS Inter-Module Comm
Status
30567 1
0 = Failed
1 = Normal
1+N, SCC
MMS Event Summary 30568 1
0 = None
1 = Alarm
2 = Fault
1+N, SCC
MMS Module Inverter Status 30569 1 0 = off 1 = on 1+N, SCC
MMS Module Output Voltage Status 30570 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
1+N, SCC
MMS Module Output Source 30571 1
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
1+N, SCC
MMS Module Total kW Output 30572 1 Units : kW SCC
MMS Module Total kVA Output 30573 1 Units : kVA SCC
MMS Module DC Bus Voltage 30574 1 Units : VDC SCC
MMS Module Battery Current 30575 1 Units : A DC SCC
MMS Module Battery Time
Remaining
30576 1 Units : min SCC
ModuleList 8
MMS Inter-Module Comm
Status
30645 1
0 = Failed
1 = Normal
1+N, SCC
MMS Event Summary 30646 1
0 = None
1 = Alarm
2 = Fault
1+N, SCC
MMS Module Inverter Status 30647 1 0 = off 1 = on 1+N, SCC
MMS Module Output Voltage
Status
30648 1
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
1+N, SCC
MMS Module Output Source 30649 1
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
1+N, SCC
MMS Module Total kW Output 30650 1 Units : kW SCC
Table 56 Liebert NXL
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types