Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
125 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Output
Output Overload 10050 1 Active on Alarm
Output Off Pending 10051 1 Active on Alarm
System Output Off 10052 1 Active on Alarm
System Shutdown - Transformer Over Temperature 10053 1 Active on Alarm
Inverter Shutdown - Overload 10054 1 Active on Alarm
System Shutdown - Output Short 10055 1 Active on Alarm
System Shutdown - Low Battery 10056 1 Active on Alarm
System Shutdown - Remote Shutdown 10057 1 Active on Alarm
System Shutdown - Hardware Fault 10058 1 Active on Alarm
Maximum Load Alarm 10059 Active on Alarm
Inverter
Loss of Redundancy 10070 1 Active on Alarm
Power Module Failure 10071 1 Active on Alarm
Power Module Warning 10072 1 Active on Alarm
System Status
Unspecified General Event 10083 1 Active on Alarm
Check Air Filter 10084 1 Active on Alarm
Frame Fan Fault 10085 1 Active on Alarm
Transformer Fan Fault 10086 1 Active on Alarm
Transformer Overtemperature 10087 1 Active on Alarm
No Load Warning 10088 1 Active on Alarm
PowerModule 1
Power Module Fan Fault 10099 1 Active on Alarm
Power Module Over Temperature 10100 1 Active on Alarm
Power Module Shutdown - Over Temperature 10101 1 Active on Alarm
PowerModule 10
Power Module Fan Fault 10216 1 Active on Alarm
Power Module Over Temperature 10217 1 Active on Alarm
Power Module Shutdown - Over Temperature 10218 1 Active on Alarm
BatteryModule 1
Battery Module Temperature Sensor Fault 10229 1 Active on Alarm
Battery Module Over Temperature 10230 1 Active on Alarm
Replace Battery Module 10231 1 Active on Alarm
BatteryModule 2
Battery Module Temperature Sensor Fault 10242 1 Active on Alarm
Battery Module Over Temperature 10243 1 Active on Alarm
Replace Battery Module 10244 1 Active on Alarm
BatteryModule 80
Battery Module Temperature Sensor Fault 11256 1 Active on Alarm
Battery Module Over Temperature 11257 1 Active on Alarm
Replace Battery Module 11258 1 Active on Alar
ChargerModule
Charger Module Fan Fault 11269 1 Active on Alarm
Table 43 Liebert APS
- Status and Coil (continued)
Data Label
Status Coil
Number
of Bits Notes