Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
233 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Remote Sensor Average
Temperature
Analog_Value 314 5007_1 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor Average
Temperature
Analog_Value 10314 5007_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Remote Sensor Maximum
Temperature
Analog_Value 315 5006_1 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor Maximum
Temperature
Analog_Value 10315 5006_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Remote Sensor System
Average Temperature
Analog_Value 316 5591_1 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor System
Average Temperature
Analog_Value 10316 5591_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Remote Sensor System
Maximum Temperature
Analog_Value 317 5592_1 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor System
Maximum Temperature
Analog_Value 10317 5592_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 1
Remote Sensor Temperature Analog_Value 329 5059_1_1 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor Temperature Analog_Value 10329
5059_1_1_deg
_F
RD Units: deg F
2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 2
Remote Sensor Temperature Analog_Value 341 5059_1_2 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor Temperature Analog_Value 10341
5059_1_2_deg
_F
RD Units: deg F
2, 3, 4,
5, 6
Remote Sensors - Remote Sensor 10
Remote Sensor Temperature Analog_Value 437 5059_1_10 RD Units: deg C
2, 3, 4,
5, 6
Remote Sensor Temperature Analog_Value 10437
5059_1_10_de
g_F
RD Units: deg F
2, 3, 4,
5, 6
Static Pressure
Static Pressure Set Point Analog_Value 461 5626_1 RW Units: Pa 3, 6
Unit Static Pressure Analog_Value 462 5627_1 RD Units: Pa 3, 6
System Static Pressure Analog_Value 463 5628_1 RD Units: Pa 3, 6
EconoPhase - Pump 1
Pump Hours Analog_Value 523 5298_1_1 RW Units: hr 5
EconoPhase - Pump 2
Pump Hours Analog_Value 526 5298_1_2 RW Units: hr 5
Global Condensers - GC Low Noise Mode
Condenser Low Noise Mode
Max Fan Speed
Analog_Value 529 5548_1_1 RW Units: %
3, 4, 5,
6
Condenser Normal Mode Max
Fan Speed
Analog_Value 530 5549_1_1 RW Units: %
3, 4, 5,
6
Condenser Low Noise Mode
Start Time
Analog_Value 531 5552_1_1 RW
Units: Seconds
since Midnight
3, 4, 5,
6
Condenser Low Noise Mode
Stop Time
Analog_Value 532 5553_1_1 RW
Units: Seconds
since Midnight
3, 4, 5,
6
Table 78 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes