Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
107 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Subfeed 1
Subfeed Current Ix 34619 — 1 — A AC
Subfeed Current Iy 34620 — 1 — A AC
Subfeed Current Iz 34621 — 1 — A AC
Subfeed Neutral Current 34622 — 1 — A AC
Subfeed Ground Current 34623 — 1 10 A AC
Subfeed Output Power (kVA) 34624 — 1 — kVA
Subfeed Output Power (kW) 34625 — 1 — kW
Subfeed Output kW-Hrs 34626 44626 2 10 kWH
Subfeed Power Factor 34628 — 1 100 —
Subfeed Output Percent Load 34629 — 1 - %
Subfeed Current Ix THD 34630 — 1 10 %
Subfeed Current Iy THD 34631 — 1 10 %
Subfeed Current Iz THD 34632 — 1 10 %
Subfeed Current Ix Crest Factor 34633 — 1 10 —
Subfeed Current Iy Crest Factor 34634 — 1 10 —
Subfeed Current Iz Crest Factor 34635 — 1 10 —
Subfeed 2
Subfeed Current Ix 34639 — 1 — A AC
Subfeed Current Iy 34640 — 1 — A AC
Subfeed Current Iz 34641 — 1 — A AC
Subfeed Neutral Current 34642 — 1 — A AC
Subfeed Ground Current 34643 — 1 10 A AC
Subfeed Output Power (kVA) 34644 — 1 — kVA
Subfeed Output Power (kW) 34645 — 1 — kW
Subfeed Output kW-Hrs 34646 44646 2 10 kWH
Subfeed Power Factor 34648 — 1 100 —
Subfeed Output Percent Load 34649 — 1 - %
Subfeed Current Ix THD 34650 — 1 10 %
Subfeed Current Iy THD 34651 — 1 10 %
Subfeed Current Iz THD 34652 — 1 10 %
Subfeed Current Ix Crest Factor 34653 — 1 10 —
Subfeed Current Iy Crest Factor 34654 — 1 10 —
Subfeed Current Iz Crest Factor 34655 — 1 10 —
Table 36 Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units