Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
107 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Subfeed 1
Subfeed Current Ix 34619 1 A AC
Subfeed Current Iy 34620 1 A AC
Subfeed Current Iz 34621 1 A AC
Subfeed Neutral Current 34622 1 A AC
Subfeed Ground Current 34623 1 10 A AC
Subfeed Output Power (kVA) 34624 1 kVA
Subfeed Output Power (kW) 34625 1 kW
Subfeed Output kW-Hrs 34626 44626 2 10 kWH
Subfeed Power Factor 34628 1 100
Subfeed Output Percent Load 34629 1 - %
Subfeed Current Ix THD 34630 1 10 %
Subfeed Current Iy THD 34631 1 10 %
Subfeed Current Iz THD 34632 1 10 %
Subfeed Current Ix Crest Factor 34633 1 10
Subfeed Current Iy Crest Factor 34634 1 10
Subfeed Current Iz Crest Factor 34635 1 10
Subfeed 2
Subfeed Current Ix 34639 1 A AC
Subfeed Current Iy 34640 1 A AC
Subfeed Current Iz 34641 1 A AC
Subfeed Neutral Current 34642 1 A AC
Subfeed Ground Current 34643 1 10 A AC
Subfeed Output Power (kVA) 34644 1 kVA
Subfeed Output Power (kW) 34645 1 kW
Subfeed Output kW-Hrs 34646 44646 2 10 kWH
Subfeed Power Factor 34648 1 100
Subfeed Output Percent Load 34649 1 - %
Subfeed Current Ix THD 34650 1 10 %
Subfeed Current Iy THD 34651 1 10 %
Subfeed Current Iz THD 34652 1 10 %
Subfeed Current Ix Crest Factor 34653 1 10
Subfeed Current Iy Crest Factor 34654 1 10
Subfeed Current Iz Crest Factor 34655 1 10
Table 36 Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units