Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 196
Bypass Current L2 30210 — 1 — A
Output Voltage L2 30213 — 1 — V
Output Current L2 30214 — 1 — A
Input Voltage L3 30253 — 1 — V
Input Current L3 30254 — 1 — A
Bypass Voltage L3 30259 — 1 — V
Bypass Current L3 30260 — 1 — A
Output Voltage L3 30263 — 1 — V
Output Current L3 30264 — 1 — A
Black Out Count 30301 — 1 — —
Brown Out Count 30302 — 1 — —
Transient Count 30301 — 1 — —
Silent Audible Alarm — 40101 — — Any value
Battery Start — 40102 1 — 1=Start, 0=Abort
Open UPS Output Switch — 40104 — —
Delay time in Seconds, last digit will be
ignored
Reboot UPS Output Switch — 40105 1 —
Delay time in Seconds, last digit will be
ignored
Close UPS Output Switch — 40106 — —
Delay time in Seconds, last digit will be
ignored
Transfer Load to Bypass — 40107 1 — Any value
Transfer Load to Inverter — 40108 — — Any value
Reset UPS Statistic data — 40111 1 — Any value
Turn UPS Outlets On — 40112 1 —
Bitmap mask for Outlet 1-16. All bits set to 1
will be turned On
Turn UPS Outlets Off — 40113 1 —
Bitmap mask for Outlet 1-16. All bits set to 1
will be turned Off
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 66 Liebert Series 300
™
UPS - Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units