Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
19 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Compressor Low Suction Pressure - Event
Type 1
30337 40337 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure - Event
Type 2
30338 40338 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Control 1
30339 40339 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Control 2
30340 40340 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Type 1
30341 40341 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Type 2
30342 40342 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Control 1 30343 40343 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Control 2 30344 40344 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Type 1 30345 40345 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Type 2 30346 40346 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Control 1
30347 40347 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Control 2
30348 40348 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Type 1
30349 40349 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Type 2
30350 40350 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Ctrl 1
30351 40351 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Ctrl 2
30352 40352 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Type 1
30353 40353 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Type 2
30354 40354 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A High Humidity - Event
Control
30355 40355 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Air Sensor A High Humidity - Event
Type
30356 40356 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes