Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 12
Condenser Circuit Unspecified General Event 10494 1 Active on Alarm 3, 4, 5, 6
Input Undervoltage 1 10500 1 Active on Alarm 6
Input Undervoltage 2 10501 1 Active on Alarm 6
Input Undervoltage 3 10502 1 Active on Alarm 6
Input Undervoltage 4 10503 1 Active on Alarm 6
Input Undervoltage 5 10504 1 Active on Alarm 6
Input Undervoltage 6 10505 1 Active on Alarm 6
Return Humidity Sensor Issue 10600 1 Active on Alarm 5, 6
Compressor Low Differential Pressure Lockout 1 10601 1 Active on Alarm 5
Compressor Low Differential Pressure Lockout 2 10602 1 Active on Alarm 5
Airflow Sensor Issue 10603 1 Active on Alarm 5, 6
Ext Air Damper Position Issue 10604 1 Active on Alarm 5, 6
Ext Power Source A Failure 10605 1 Active on Alarm 5, 6
Ext Power Source B Failure 10606 1 Active on Alarm 5, 6
Static Pressure Sensor Out of Range 10607 1 Active on Alarm 5, 6
Fluid Temperature Sensor Issue 1 10608 1 Active on Alarm 6
Fluid Temperature Sensor Issue 2 10609 1 Active on Alarm 6
Fluid Flow Sensor Issue 1 10610 1 Active on Alarm 6
Fluid Flow Sensor Issue 2 10611 1 Active on Alarm 6
Mixed Mode Lockout 10620 1 Active on Alarm 5
Table 7 Extra notes key to Table 6
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 6 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes / Units Extra Notes