Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 200
Table 70 Liebert Series 610 SCC UPS - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 — Bits 12 - 15
Number of Bypass Lines 30004 40004 1 — Bits 4 - 7
Number of Output Lines 30004 40004 1 — Bits 8 - 11
Nominal Power Rating 30021 40021 2 — VA
Nominal Input Voltage 30027 40027 1 — V
Nominal Output Voltage 30028 40028 1 — V
Nominal Static Bypass Switch Voltage 30029 40029 1 — V
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 -
Silence Alarm — 40101 1 — -
Load (Apparent Power) 30102 — 2 — VA
Load (Real Power) 30104 — 2 — W
Load / Capacity 30106 — 1 — %
Output Frequency 30108 — 1 10 Hz
Bypass Frequency 30109 — 1 10 Hz
Input Voltage L1 30153 — 1 — V
Bypass Voltage L1 30159 — 1 — V
Bypass Current L1 30160 — 1 — A
Output Voltage L1 30163 — 1 — V
Output Current L1 30164 — 1 — A
Input Voltage L2 30203 — 1 — V
Bypass Voltage L2 30209 — 1 — V
Bypass Current L2 30210 — 1 — A
Output Voltage L2 30213 — 1 — V
Output Current L2 30214 — 1 — A
Input Voltage L3 30253 — 1 — V
Bypass Voltage L3 30259 — 1 — V
Bypass Current L3 30260 — 1 — A
Output Voltage L3 30263 — 1 — V
Output Current L3 30264 — 1 — A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.