Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
135 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
System Output Power L2 The system output power on Line 2.
System Output Power The sum total power of all system output phases
System Output RMS Current L1 The system output RMS current for Line 1
System Output RMS Current L2 The system output RMS current for Line 2
System Output Voltage RMS L1-L2 The system output RMS voltage between Lines 1 and 2
System Output Voltage RMS L1-N The system output RMS voltage between Line 1 and Neutral
System Output Voltage RMS L2-N The system output RMS voltage between Line 2 and Neutral
System Set To Operate With
If this point reports 'Redundancy' then the system is configured for redundancy and
the 'Loss of Redundancy' alarm is enabled.
System Shutdown - Hardware Fault Shutdown was due to an externally applied hardware control signal.
System Shutdown - Low Battery Shutdown was due to a low battery condition.
System Shutdown - Output Short Shutdown was due to a short on the output.
System Shutdown - Remote
Shutdown
Shutdown was due to a remote communications shutdown command.
System Shutdown - Transformer Over
Temperature
System shutdown due to transformer over temperature.
System Status The operating status for the system
Time Until Next Auto Battery Test The time until the next automatic battery test is started.
Transformer Fan Fault The transformer fan has failed.
Transformer Overtemperature Transformer temperature has exceeded the limit
Unspecified General Event One or more unspecified events active. See local unit display for further details.
UPS Battery Status UPS battery status
UPS Output on Bypass The output power is supplied by the bypass
UPS Output Source UPS output source
Table 45 Liebert APS
- Glossary (continued)
Data Label Data Description