Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 202
Rectifier Block — 40290 1 — Bit 7
Rectifier Current Limit — 40290 1 — Bit 8
Rectifier Overtemperature — 40290 1 — Bit 9
Rectifier Fuse Failure — 40290 1 — Bit 10
Inverter Voltage Fault — 40291 1 — Bit 0
Inverter Disable — 40291 1 — Bit 1
Inverter Disable — 40291 1 — Bit 2
Inverter Current Limit — 40291 1 — Bit 3
Inverter Overtemperature — 40291 1 — Bit 4
Inverter Non Sync — 40291 1 — Bit 5
Inverter Overvoltage — 40291 1 — Bit 6
Inverter Undervoltage — 40291 1 — Bit 7
Inverter Fuse Failure — 40291 1 — Bit 8
Output Overvoltage — 40291 1 — Bit 9
Output Undervoltage — 40291 1 — Bit 10
Output Undervoltage — 40292 1 — Bit 0
Output Waveform Error — 40292 1 — Bit 1
Inverter Frequency Error — 40292 1 — Bit 2
Inverter Parallel Error — 40292 1 — Bit 3
Contactor Failure — 40292 1 — Bit 4
Battery Test — 40292 1 — Bit 5
Battery Test Failed — 40292 1 — Bit 6
Battery On Load — 40292 1 — Bit 7
Battery End of Discharge — 40292 1 — Bit 8
Boost Time Expired — 40292 1 — Bit 9
DC Overvoltage — 40292 1 — Bit 10
DC Undervoltage — 40293 1 — Bit 0
Battery Fuse Failure — 40293 1 — Bit 1
DC Overvoltage — 40293 1 — Bit 2
Transfer Count Block — 40293 1 — Bit 3
Overload Shutdown — 40293 1 — Bit 4
Overtemperature SD — 40293 1 — Bit 5
Emergency Stop — 40293 1 — Bit 6
Overload Present — 40293 1 — Bit 7
Overload Shutdown TO — 40293 1 — Bit 8
Display Error — 40293 1 — Bit 9
Display Error — 40293 1 — Bit 10
Inverter Over Capacity — 40293 1 — Bit 11
Bypass ECO Mode — 40293 1 — Bit 12
Fan Failure — 40293 1 — Bit 13
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 71 Liebert HiPulse
™,
Liebert SICE 7200
™
- Input and Holding - SMM/SSM (continued)
Controller Multi Module Series - SMM
Liebert Products
Liebert HiPulse
Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units