Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 262
Table 85 Liebert CRV
- Multistate Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes
Protocol
Server Class MultiState_Value 1 4553_1 RD
1 = UPS
2 = AIR
3 = PMP
4 = PDU
Air Temperature
Air Temperature Control Sensor MultiState_Value 12 5012_1 RW
1 = Supply
2 = Remote
3 = Return
Remote Sensor Temperature
Calculation
MultiState_Value 13 5013_1 RW
1 = Average
2 = Maximum
Fans
Fan Control Mode MultiState_Value 24 5047_1 RW
1 = Internal (Auto)
2 = External (Manual)
Fan Control Sensor MultiState_Value 25 5052_1 RW
1 = Supply
2 = Remote
3 = Return
Remote Sensors 1
Remote Sensor Function MultiState_Value 36 5058_1 RW
1 = Disable
2 = Reference
3 = Control
Remote Sensors 1
Remote Sensor Function MultiState_Value 47 5058_2 RW
1 = Disable
2 = Reference
3 = Control
Remote Sensors 10
Remote Sensor Function MultiState_Value 135 5058_10 RW
1 = Disable
2 = Reference
3 = Control
System Info
System Status MultiState_Value 146 4123_1 RD
1 = Normal Operation
2 = StartUp
3 = Normal
with Warning
4 = Normal with Alarm
5 = Abnormal Operation
System Operating State MultiState_Value 147 4706_1 RD
1 = off
2 = on
3 = standby
System Control Mode MultiState_Value 148 4707_1 RD
1 = Internal (Auto)
2 = External (Manual)
System Operating State Reason MultiState_Value 149 5074_1 RD
1 = Reason Unknown
2 = Network Display
3 = Alarm
4 = Schedule
5 = Remote System
6 = External Input
7 = Local Display
System Operations
System On/Off Control MultiState_Value 160 5143_1 RW
1 = off
2 = on