Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
287 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Fan Button Control Multistate_Value 175 5488_2 RW
1 = Enabled
2 = Disabled
Visual ID Control Multistate_Value 176 5489_2 RW
1 = Disabled
2 = Enabled
Ext System Condensation Detected - Event
Control
Multistate_Value 177 5493_2 RW
1 = Disabled
2 = Enabled
Ext System Condensation Detected - Event Type Multistate_Value 178 5494_2 RW
1 = Message
2 = Warning
3 = Alarm
Ext Fan Issue - Event Control Multistate_Value 179 5496_2 RW
1 = Disabled
2 = Enabled
Ext Fan Issue - Event Type Multistate_Value 180 5497_2 RW
1 = Message
2 = Warning
3 = Alarm
Sensor Issue - Event Control Multistate_Value 181 5498_2 RW
1 = Disabled
2 = Enabled
Sensor Issue - Event Type Multistate_Value 182 5499_2 RW
1 = Message
2 = Warning
3 = Alarm
Ext Remote Shutdown - Event Control Multistate_Value 183 5501_2 RW
1 = Disabled
2 = Enabled
Ext Remote Shutdown - Event Type Multistate_Value 184 5502_2 RW
1 = Message
2 = Warning
3 = Alarm
XD System 2 Secondary Fans 1
Fan State Multistate_Value 195 5510_2_1 RD
1 = Off / 2 = On
3 = Economy
Fan Economy Mode Multistate_Value 196 5511_2_1 RW
1 = Disabled
2 = Automatic
3 = Manual
XD System 20
Communication Status Multistate_Value 802 5486_20 RD
1 = Connected
2 = Not Connected
Fan On/Off Control Multistate_Value 803 5487_20 RW 1 = Off / 2 = On
Primary Fan Group State Multistate_Value 804 5509_20 RD
1 = Off / 2 = On
3 = Economy
Fan Button Control Multistate_Value 805 5488_20 RW
1 = Enabled
2 = Disabled
Visual ID Control Multistate_Value 806 5489_20 RW
1 = Disabled
2 = Enabled
Ext System Condensation Detected - Event
Control
Multistate_Value 807 5493_20 RW
1 = Disabled
2 = Enabled
Ext System Condensation Detected - Event Type Multistate_Value 808 5494_20 RW
1 = Message
2 = Warning
3 = Alarm
Ext Fan Issue - Event Control Multistate_Value 809 5496_20 RW
1 = Disabled
2 = Enabled
Ext Fan Issue - Event Type Multistate_Value 810 5497_20 RW
1 = Message
2 = Warning
3 = Alarm
Sensor Issue - Event Control Multistate_Value 811 5498_20 RW
1 = Disabled
2 = Enabled
Table 94 Liebert XDP
, Liebert XDC
- Multistate Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes