Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 64
Hot Aisle Over Temp Threshold 30459 40459 1 Units : deg C
Hot Aisle Over Temp Threshold 30460 40460 1 Units : deg F
Hot Aisle Under Temp Threshold 30461 40461 1 Units : deg C
Hot Aisle Under Temp Threshold 30462 40462 1 Units : deg F
Cold Aisle Over Temp Threshold 30463 40463 1 Units : deg C
Cold Aisle Over Temp Threshold 30464 40464 1 Units : deg F
Cold Aisle Under Temp Threshold 30465 40465 1 Units : deg C
Cold Aisle Under Temp Threshold 30466 40466 1 Units : deg F
XD System 2
Communication Status 30472 1
0 = Connected
1 = Not Connected
Fan On/Off Control 30473 40473 1
0 = off
1 = on
Primary Fan Group State 30474 1
0 = off
1 = on
2 = economy
Fan Button Control 30475 40475 1
0 = enabled
1 = disabled
Visual ID Control 30476 40476 1
0 = disabled
1 = enabled
Cooling Capacity 30477 1 Units : %
Cooling Capacity 30478 1 Units : kW
Ext System Condensation Detected - Event Control 30479 40479 1
0 = disabled
1 = enabled
Ext System Condensation Detected - Event Type 30480 40480 1
0 = Message
1 = Warning
2 = Alarm
Ext Fan Issue - Event Control 30481 40481 1
0 = disabled
1 = enabled
Ext Fan Issue - Event Type 30482 40482 1
0 = Message
1 = Warning
2 = Alarm
Sensor Issue - Event Control 30483 40483 1
0 = disabled
1 = enabled
Sensor Issue - Event Type 30484 40484 1
0 = Message
1 = Warning
2 = Alarm
Ext Remote Shutdown - Event Control 30485 40485 1
0 = disabled
1 = enabled
Ext Remote Shutdown - Event Type 30486 40486 1
0 = Message
1 = Warning
2 = Alarm
Hot Aisle Over Temp Threshold 30487 40487 1 Units : deg C
Hot Aisle Over Temp Threshold 30488 40488 1 Units : deg F
Hot Aisle Under Temp Threshold 30489 40489 1 Units : deg C
Hot Aisle Under Temp Threshold 30490 40490 1 Units : deg F
Cold Aisle Over Temp Threshold 30491 40491 1 Units : deg C
Cold Aisle Over Temp Threshold 30492 40492 1 Units : deg F
Cold Aisle Under Temp Threshold 30493 40493 1 Units : deg C
Cold Aisle Under Temp Threshold 30494 40494 1 Units : deg F
Table 21 Liebert XDP
- Input and Holding (continued)
Data Label
Input Holding # of Reg Scale Notes/Units