Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 92
Table 32 Liebert Atlas Air
, Liebert Atlas PEC
, Liebert CEMS 100
- Input and Holding - C100 4-step
Controller CEMS 100
Liebert Products
Liebert Atlas Air
Liebert Atlas PEC
Liebert CEMS 100
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Unit Number 40001 1 1-99
Average Return Air Temp. 40002 1 10 deg C
Average Return Air Humidity 40003 1 10 %
Average Supply Air Temp. 40004 1 10 deg C
Average Supply Air Humidity 40005 1 10 %
Fan Status 40007 1 1=On / 0=Off
Cool 1 Status 40008:0 1 1=On / 0=Off
Cool 2 Status 40009:0 1 1=On / 0=Off
Cool 3 Status 40008:4 1 1=On / 0=Off
Cool 4 Status 40009:4 1 1=On / 0=Off
Heat 1 Status 40010 1 1=On / 0=Off
Heat 2 Status 40011 1 1=On / 0=Off
Humidifier Status 40012 1
De-humidifier Status 40013 1
Cooling Capacity 40014 1 %
Heating Capacity 40015 1 %
Temperature Control Status 40019 1 0=Return / 1=Supply
Battery Voltage Level 40020 1 100 V
Remote Shutdown Status 40021 1 1=Enabled / 0=Disabled
Temperature Control Select 40024 1
0=Return / 1=Supply
2=Remote / 3=Auto
Alarm Points
Communications 40289 1 Bit 0
Faulty Sensor 40289 1 Bit 1
High Temperature 40289 1 Bit 2
Low Temperature 40289 1 Bit 3
High Humidity 40289 1 Bit 4
Low Humidity 40289 1 Bit 5
Loss of Airflow 40289 1 Bit 6
Water Under Floor 40289 1 Bit 7
Cool 1 Low Pressure Alarm 40289 1 Bit 8
Cool 2 Low Pressure Alarm 40289 1 Bit 9
Cool 1 High Pressure Alarm 40289 1 Bit 10
Cool 2 High Pressure Alarm 40290 1 Bit 0
Cool Service 40290 1 Bit 1
Humidifier Service 40290 1 Bit 2
Filter Service 40290 1 Bit 3