Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 126
Table 44 Liebert APS
™
- Input and Holding
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Protocol
Server Class 30385 — — —
1 = UPS
2 = AIR
3 = PMP
4 = PDU
Input
System Input RMS L1-N 30396 — 1 10
Units : VAC
Uint 16
System Input RMS L2-N 30397 — 1 10
Units : VAC
Uint 16
System Input RMS L3-N 30398 — 1 10
Units : VAC
Uint 16
System Input RMS L1-L2 30399 — 1 10
Units : VAC
Uint 16
System Input RMS L2-L3 30400 — 1 10
Units : VAC
Uint 16
System Input RMS L3-L1 30401 — 1 10
Units : VAC
Uint 16
System Input RMS Current L1 30402 — 1 10
Units : A AC
Uint 16
System Input RMS Current L2 30403 — 1 10
Units : A AC
Uint 16
System Input RMS Current L3 30404 — 1 10
Units : A AC
Uint 16
System Input Frequency 30405 — 1 100
Units : Hz
Uint 16
System Input Power Factor L1 30406 — 1 100 Uint 16
System Input Power Factor L2 30407 — 1 100 Uint 16
System Input Power Factor L3 30408 — 1 100 Uint 16
System Input Brown Out Count 30409 — 1 — Uint 16
System Input Black Out Count 30410 — 1 — Uint 16
Bypass
Bypass Input Voltage RMS L1-N 30421 — 1 10
Units : VAC
Uint 16
Bypass Input Voltage RMS L2-N 30422 — 1 10
Units : VAC
Uint 16
Bypass Input Voltage RMS L1-L2 30423 — 1 10
Units : VAC
Uint 16
Bypass Input Frequency 30424 — 1 100
Units : Hz
Uint 16
Number Of Transfers To Bypass 30425 — 1 — Uint 16
Bypass Qualification Status 30426 — 1 —
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High