Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 154
Rectifier Active Filter 30340 1
0 = Not Installed
1 = Installed
N+1, 1+N,
1+1, SMS
Rectifier Status 30341 1
0 = off
1 = on
N+1, 1+N,
1+1, SMS
System Status 30342 1
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
SCC, N+1,
1+N, 1+1,
SMS
UPS Module Type 30343 1
0 = Single Module System
1 = Module (1 + 1)
2 = Module (1 + N)
3 = Module (N + 1)
4 = System Control Cabinet
5 = Main Static Switch
SCC, N+1,
1+N, 1+1,
SMS
Static Switch Type 30344 1
0 = Not Applicable
1 = Continuous
Duty
2 = Momentary
Duty
SCC, 1+N,
1+1, SMS
System Input Power Source 30345 1
0 = None
1 = Utility (mains)
2 = Generator
SCC, N+1,
1+N, 1+1,
SMS
Output Real Power Rating 30346 2 kW
SCC, N+1,
1+N, 1+1, SMS
Input Isolation Transformer 30348 1
0 = Not Installed
1 = Installed
SCC, N+1,
1+N, 1+1, SMS
System Output Maximum Amp
Rating
30350 1 A AC
SCC, 1+N,
1+1
Output Wire Configuration 30353 1
0 = Two Wire (single phase
+ return)
1 = Two Wire
(2 phase, no neutral)
2 = Three Wire
(2 phase + neutral)
3 = Three Wire (3-phase,
no neutral)
4 = Four Wire
(3 phases + neutral)
SCC, N+1,
1+N, 1+1,
SMS
Battery Cell Count - Lead Acid 30354 1
SCC, N+1,
1+N, 1+1, SMS
Battery Cell Count-Nickel Cadmium 30355 1
SCC, N+1,
1+N, 1+1, SMS
UPS System Output Source 30356 1
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
SCC, 1+N,
1+1, SMS
Static Bypass Switch 30357 1 0 = off 1 = on
SCC, 1+N,
1+1, SMS
Battery Volts for Cabinet 1 30358 1 VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 2 30359 1 VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 3 30360 1 VDC
N+1, 1+N,
1+1, SMS
Table 56 Liebert NXL
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types