Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 228
Return Air Temperature Set
Point
Analog_Value 10032
5333_1_1_deg
_F
RW Units: deg F 1
Return Air Over Temp Threshold Analog_Value 33 5022_1_1 RW Units: deg C
1, 2, 3,
4, 5, 6
Return Air Over Temp Threshold Analog_Value 10033
5022_1_1_deg
_F
RW Units: deg F
1, 2, 3,
4, 5, 6
Return Air Under Temp
Threshold
Analog_Value 34 5334_1_1 RW Units: deg C
1, 2, 3,
4, 5, 6
Return Air Under Temp
Threshold
Analog_Value 10034
5334_1_1_deg
_F
RW Units: deg F
1, 2, 3,
4, 5, 6
Air - External Sensors
Ext Air Sensor A Temperature Analog_Value 45 4594_1_1 RD Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor A Temperature Analog_Value 10045
4594_1_1_deg
_F
RD Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor B Temperature Analog_Value 46 4597_1_1 RD Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor B Temperature Analog_Value 10046
4597_1_1_deg
_F
RD Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor C Temperature Analog_Value 47 5336_1_1 RD Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor C Temperature Analog_Value 10047
5336_1_1_deg
_F
RD Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor A Over Temp
Threshold
Analog_Value 48 5337_1_1 RW Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor A Over Temp
Threshold
Analog_Value 10048
5337_1_1_deg
_F
RW Units: deg F
1, 2, 3,
4, 5, 6
Ext Air Sensor A Under Temp
Threshold
Analog_Value 49 5338_1_1 RW Units: deg C
1, 2, 3,
4, 5, 6
Ext Air Sensor A Under Temp
Threshold
Analog_Value 10049
5338_1_1_deg
_F
RW Units: deg F
1, 2, 3,
4, 5, 6
Outside Air Temperature Analog_Value 50 5574_1_1 RD Units: deg C
2, 3, 4,
5, 6
Outside Air Temperature Analog_Value 10050
5574_1_1_deg
_F
RD Units: deg F
2, 3, 4,
5, 6
Humidity
Return Humidity Analog_Value 60 5028_1 RD Units: % RH
1, 2, 3,
4, 5, 6
Humidity Set Point Analog_Value 61 5029_1 RW Units: % RH
1, 2, 3,
4, 5, 6
Return Humidity Set Point Analog_Value 62 5339_1 RW Units: % RH 1
Humidity Proportional Band Analog_Value 63 5341_1 RW Units: % RH
1, 2, 3,
4, 5, 6
Humidity Dead Band Analog_Value 64 5032_1 RW Units: % RH
1, 2, 3,
4, 5, 6
Humidity Proportional Control
Integration Time
Analog_Value 65 5342_1 RW Units: min
1, 2, 3,
4, 5, 6
High Return Humidity Threshold Analog_Value 66 5033_1 RW Units: % RH
1, 2, 3,
4, 5, 6
Low Return Humidity Threshold Analog_Value 67 5035_1 RW Units: % RH
1, 2, 3,
4, 5, 6
Table 78 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes