Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 348
Table 112 Liebert NXL
- 50 Hz, CE version (Models 48 and 49)—Multistate Data
Data Label
Object Type Instance Object Name Access Notes
Input
Input Qualification Status MultiState_Value 1 4735_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
Bypass
Static Bypass Switch MultiState_Value 12 4736_1 RD
1 = off
2 = on
Bypass Qualification Status MultiState_Value 13 4737_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
Battery
UPS Battery Status MultiState_Value 24 4871_1 RD
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
The main battery disconnect status. MultiState_Value 25 5872_1 RD
1 = Open
2 = Closed
3 = Disabled
Battery SCR Status MultiState_Value 26 5876_1 RD
1 = OK
2 = Fault
3 = unknown
Main Battery Disconnect Switch Lock
Status
MultiState_Value 27 5877_1 RD
1 = Locked
2 = Unlocked
3 = unknown
DC Bus
DC Bus Qualification Status MultiState_Value 38 4743_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
Output
Output Qualification Status MultiState_Value 49 4744_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
Inverter
Inverter Output Qualification Status MultiState_Value 60 4745_1 RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
Inverter On/Off State MultiState_Value 61 4746_1 RD
1 = off
2 = on
Rectifier
Rectifier Pulse Count MultiState_Value 72 4257_1 RD
1 = 6 Pulse
2 = 12 Pulse
3 = 18 Pulse
4 = 24 Pulse
Rectifier Input Passive Filter MultiState_Value 73 4258_1 RD
1 = Not Installed
2 = Installed
Rectifier Passive Filter Switch MultiState_Value 74 4301_1 RD
1 = Not Installed
2 = Installed
Rectifier Active Filter MultiState_Value 75 4302_1 RD
1 = Not Installed
2 = Installed
Rectifier Status MultiState_Value 76 4748_1 RD
1 = off
2 = on