Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 208
Thermal Runaway Charger Current Level One Event
String 1 - 32
13297-13328 1 Active on Alarm
Thermal Runaway Charger Current Level Two Event
String 1 - 32
13329-13360 1 Active on Alarm
Ground Fault Detected
String 1 - 32
14041-14072 1 Active on Alarm
Cell Entity (Cells 1 – 320)
Low Cell Voltage
Cell 1 - 320
10673-10992 1 Active on Alarm
High Cell Voltage
Cell 1 - 320
10993-11312 1 Active on Alarm
Low Cell Temperature
Cell 1 - 320
11313-11632 1 Active on Alarm
High Cell Temperature
Cell 1 - 320
11633-11952 1 Active on Alarm
Low Internal Resistance
Cell 1 - 320
11953-12272 1 Active on Alarm
High Internal Resistance
Cell 1 - 320
12273-12592 1 Active on Alarm
High Intercell Resistance
Cell 1 - 320
12593-12912 1 Active on Alarm
Discharge Low Cell Voltage
Cell 1 - 320
12913-13232 1 Active on Alarm
Intertier Resistance High
Cell 1 - 320
13361-13680 1 Active on Alarm
Cell Entity (Cells 321 – 360)
Low Cell Voltage
Cell 321 - 360
13681-13720 1 Active on Alarm
High Cell Voltage
Cell 321 – 360
13721-13760 1 Active on Alarm
Low Cell Temperature
Cell 321 – 360
13761-13800 1 Active on Alarm
High Cell Temperature
Cell 321 – 360
13801-13840 1 Active on Alarm
Low Internal Resistance
Cell 321 – 360
13841-13780 1 Active on Alarm
High Internal Resistance
Cell 321 – 360
13881-13920 1 Active on Alarm
High Intercell Resistance
Cell 321 – 360
13921-12860 1 Active on Alarm
Discharge Low Cell Voltage
Cell 321 – 360
13961-14000 1 Active on Alarm
Intertier Resistance High
Cell 321 - 360
14001-14040 1 Active on Alarm
Table 74 Alber
®
BDSU
- Status and Coil
Data Description
Status Coil
Number
of Bits Notes / Units