Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
205 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 73 Liebert Npower
- Input and Holding - IMP
Controller Single Module Series - SMS
Liebert Products Liebert Npower - SMS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Input Voltage A-B 40001 1 V
Input Voltage B-C 40002 1 V
Input Voltage C-A 40003 1 V
Bypass Voltage A-B 40004 1 V
Bypass Voltage B-C 40005 1 V
Bypass Voltage C-A 40006 1 V
Battery Voltage 40007 1 V
Battery Current 40008 1 10 A
Battery Temperature 40009 1 deg C
Output Voltage A-B 40010 1 V
Output Voltage B-C 40011 1 V
Output Voltage C-A 40012 1 V
Output Current A 40013 1 10 A
Output Current B 40014 1 10 A
Output Current C 40015 1 10 A
Output kVA A 40016 1 kVA
Output kVA B 40017 1 kVA
Output kVA C 40018 1 kVA
Output kW A 40019 1 kW
Output kW B 40020 1 kW
Output kW C 40021 1 kW
Output Frequency 40022 1 10 Hz
Rated kVA Percentage 40023 1 %
Rated kW Percentage 40024 1 %
Alarm Points
Communications Loss 40289 1 Bit 0
Battery Fuse Fail 40289 1 Bit 1
Battery Low Transfer 40289 1 Bit 2
DC Over Voltage Transient 40289 1 Bit 3
Input Phase Rotation Error 40289 1 Bit 4
Rectifier/Trap Fuse Fail 40289 1
Bit 5
Any of Rectifier / Trap Fuse
Bypass Frequency Error 40289 1 Bit 6
Bypass Overload Shutdown 40289 1 Bit 7
Bypass Phase Rotation Error 40289 1 Bit 8
Inverter Over Voltage Transfer 40289 1 Bit 9
Inverter Fuse Fail 40289 1 Bit 10
Output Over Voltage Transfer 40289 1 Bit 11
Output Under Voltage Transfer 40289 1 Bit 12
SBS SCR Open 40289 1 Bit 13
SBS SCR Short 40289 1 Bit 14
Inverter Over Current Transfer 40289 1 Bit 15