Modbus 485 and Modbus IP Protocols - UPS Systems
205 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 73 Liebert Npower
™
- Input and Holding - IMP
Controller Single Module Series - SMS
Liebert Products Liebert Npower - SMS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Input Voltage A-B — 40001 1 — V
Input Voltage B-C — 40002 1 — V
Input Voltage C-A — 40003 1 — V
Bypass Voltage A-B — 40004 1 — V
Bypass Voltage B-C — 40005 1 — V
Bypass Voltage C-A — 40006 1 — V
Battery Voltage — 40007 1 — V
Battery Current — 40008 1 10 A
Battery Temperature — 40009 1 — deg C
Output Voltage A-B — 40010 1 — V
Output Voltage B-C — 40011 1 — V
Output Voltage C-A — 40012 1 — V
Output Current A — 40013 1 10 A
Output Current B — 40014 1 10 A
Output Current C — 40015 1 10 A
Output kVA A — 40016 1 — kVA
Output kVA B — 40017 1 — kVA
Output kVA C — 40018 1 — kVA
Output kW A — 40019 1 — kW
Output kW B — 40020 1 — kW
Output kW C — 40021 1 — kW
Output Frequency — 40022 1 10 Hz
Rated kVA Percentage — 40023 1 — %
Rated kW Percentage — 40024 1 — %
Alarm Points
Communications Loss — 40289 1 — Bit 0
Battery Fuse Fail — 40289 1 — Bit 1
Battery Low Transfer — 40289 1 — Bit 2
DC Over Voltage Transient — 40289 1 — Bit 3
Input Phase Rotation Error — 40289 1 — Bit 4
Rectifier/Trap Fuse Fail — 40289 1 —
Bit 5
Any of Rectifier / Trap Fuse
Bypass Frequency Error — 40289 1 — Bit 6
Bypass Overload Shutdown — 40289 1 — Bit 7
Bypass Phase Rotation Error — 40289 1 — Bit 8
Inverter Over Voltage Transfer — 40289 1 — Bit 9
Inverter Fuse Fail — 40289 1 — Bit 10
Output Over Voltage Transfer — 40289 1 — Bit 11
Output Under Voltage Transfer — 40289 1 — Bit 12
SBS SCR Open — 40289 1 — Bit 13
SBS SCR Short — 40289 1 — Bit 14
Inverter Over Current Transfer — 40289 1 — Bit 15