Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 256
Table 83 Liebert CRV
- Binary Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes
Air Temperature
Supply Air Over Temperature Binary_Value 1 5015_1 RD Active on Alarm
Supply Air Under Temperature Binary_Value 2 5019_1 RD Active on Alarm
Return Air Over Temperature Binary_Value 3 5023_1 RD Active on Alarm
Supply Air Sensor Issue Binary_Value 4 5026_1 RD Active on Alarm
Return Air Sensor Issue Binary_Value 5 5147_1 RD Active on Alarm
Humidity
High Return Humidity Binary_Value 16 5034_1 RD Active on Alarm
Low Return Humidity Binary_Value 17 5036_1 RD Active on Alarm
Humidifier Hours Exceeded Binary_Value 18 5037_1 RD Active on Alarm
Dehumidifier Hours Exceeded Binary_Value 19 5038_1 RD Active on Alarm
Humidifier Under Current Binary_Value 20 5039_1 RD Active on Alarm
Humidifier Over Current Binary_Value 21 5040_1 RD Active on Alarm
Humidifier Low Water Binary_Value 22 5041_1 RD Active on Alarm
Humidifier Cylinder Worn Binary_Value 23 5042_1 RD Active on Alarm
Humidifier Issue Binary_Value 24 5043_1 RD Active on Alarm
Ext Humidifier Lockout Binary_Value 25 5044_1 RD Active on Alarm
Humidifier Control Board Not Detected Binary_Value 26 5045_1 RD Active on Alarm
Return Humidity Out Of Proportional Band Binary_Value 27 5046_1 RD Active on Alarm
Fans
Loss of Air Flow Binary_Value 38 5053_1 RD Active on Alarm
Fan Hours Exceeded Binary_Value 39 5054_1 RD Active on Alarm
Top Fan Issue Binary_Value 40 5055_1 RD Active on Alarm
Bottom Fan Issue Binary_Value 41 5056_1 RD Active on Alarm
Remote Sensors 1
Remote Sensor Issue Binary_Value 52 5060_1 RD Active on Alarm
Remote Sensors 2
Remote Sensor Issue Binary_Value 63 5060_2 RD Active on Alarm
Remote Sensors 3
Remote Sensor Issue Binary_Value 74 5060_3 RD
Remote Sensors 4
Remote Sensor Issue Binary_Value 85 5060_4 RD Active on Alarm
Remote Sensors 5
Remote Sensor Issue Binary_Value 96 5060_5 RD Active on Alarm
Remote Sensors 6
Remote Sensor Issue Binary_Value 107 5060_6 RD Active on Alarm
Remote Sensors 7
Remote Sensor Issue Binary_Value 118 5060_7 RD Active on Alarm
Remote Sensors 8
Remote Sensor Issue Binary_Value 129 5060_8 RD Active on Alarm
Remote Sensors 9
Remote Sensor Issue Binary_Value 140 5060_9 RD Active on Alarm