Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
129 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Auto Restart 40519 1
0 = disabled
1 = enabled
Auto Restart Delay 40520 1
Units : sec
Uint 16
Auto Restart Minimum Battery Setting 40521 1
0 = 0%
1 = 10%
2 = 20%
3 = 30%
4 = 40%
5 = 50%
6 = 60%
7 = 70%
8 = 80%
9 = 90%
No Load Warning Current Threshold 30522 40522 1
Units : A AC
Int16
No Load Warning Delay 30523 40523 1
Units : min
Uint 16
PowerModule 1
Module Operating Status 30534 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status 30535 1
0 = Inverter Inactive
1 = Inverter Active
PowerModule 2
Module Operating Status 30546 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status 30547 1
0 = Inverter Inactive
1 = Inverter Active
PowerModule 10
Module Operating Status 30642 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status 30643 1
0 = Inverter Inactive
1 = Inverter Active
BatteryModule 1
Module Operating Status 30654 1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Battery String Voltage 30655 1 10
Units : VDC
Uint16
Battery Module Temperature 30656 1 10
Units : deg C
Int16
Battery Module Temperature 30657 1 10
Units : degF
Int16
Number of Discharge Cycles 30658 1 Uint 16
Accumulated Discharge Time 30659 1 10
Units : hr
Uint 16
Table 44 Liebert APS
- Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units