Emerson MODBUS 485 Power Supply User Manual


 
BACnet Communications - Thermal Management Products
267 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Customer Input 3 - Event Type The event type for the [Customer Input 3] event.
Customer Input 3 Customer input 3.
Customer Input 4 - Event Control
Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Customer Input 4 - Event Type The event type for the [Customer Input 4] event.
Customer Input 4 Customer input 4.
Dehumidification Proportional Band
Humidity control band above [Humidity Set Point]. If measured humidity is within
this band, dehumidification operations are proportionally controlled.
Dehumidifier Hours Exceeded Operating hours for the dehumidifier have exceeded the threshold.
Dehumidifier Utilization
Present dehumidifier utilization expressed as a percentage of the maximum
rated capacity.
Dig Scroll Comp 1 Over Temp
Digital scroll compressor 1 shut off because its head temperature has exceeded
the upper threshold.
Dig Scroll Comp 1 Temp Sensor Issue
Digital scroll compressor 1 temperature sensor is disconnected or the signal is
out of range.
Electric Reheater Hours Exceeded Operating hours for electric reheater have exceeded the threshold.
Ext Compressor Lockout - Event Control
Enable/disable the activation of the [Ext Compressor Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Compressor Lockout - Event Type The event type for the [Ext Compressor Lockout] event.
Ext Compressor Lockout The compressor is shut down and disabled by an external input signal.
Ext Condenser Pump High Water High water is detected in the condenser, as indicated by an external input signal.
Ext Humidifier Lockout - Event Control
Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Humidifier Lockout - Event Type The event type for the [Ext Humidifier Lockout] event.
Ext Humidifier Lockout The humidifier is shut down and disabled by an external input signal.
Ext Loss of Flow - Event Control
Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Ext Loss of Flow - Event Type The event type for the [Ext Loss of Flow] event.
Ext Loss of Flow Loss of flow is detected, as indicated by an external input signal.
Ext Over Temperature - Event Control
Enable/disable the activation of the [Ext Over Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Over Temperature - Event Type The event type for the [Ext Over Temperature] event.
Ext Over Temperature
A temperature has exceeded its threshold, as indicated by an external input
signal.
Ext Reheat Lockout - Event Control
Enable/disable the activation of the [Ext Reheat Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Reheat Lockout - Event Type The event type for the [Ext Reheat Lockout] event.
Ext Reheat Lockout The reheater is shut down and disabled by an external input signal.
Ext Standby Glycol Pump On The standby glycol pump is on, as indicated by an external input signal.
External Fire Detected Fire detected, as indicated by an external input signal.
Fan Control Mode
Fan control mode. Allowable modes are: (0) Auto - Fan speed is controlled via
the selected fan control sensor, and, (1) Manual - Fan will operate at a fixed
speed.
Fan Control Sensor
Sensor from which air temperature measurements will be used for fan speed
control.
Table 86 Liebert CRV
- Glossary (continued)
Data Label Data Description