Modbus 485 and Modbus IP Protocols - Thermal Management Products
81 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 25 Liebert XDF
™
- Status and Coil
Controller Liebert iCOM
®
v3
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Temperature Indication
1
10011 11 1 — —
Unit Control — 25 1 — —
Reset Alarm — 26 1 — —
Acknowledge Alarm — 27 1 — —
Cabinet Sensor Alarm Enable 10023 23 1 — —
Fan On 10025 — 1 — —
Cool On 10026 — 1 — —
Compressor 1 High Pressure 10037 — 1 — —
Compressor 1 Low Pressure 10038 — 1 — —
Cond Pump-High Water 10052 — 1 — —
Loss Compressor Power 10054 — 1 — —
Emergency Damper Fail 10056 — 1 — —
High Internal Temperature 10057 — 1 — —
Loss of Power 10061 — 1 — —
Remote Shutdown 10062 — 1 — —
Unspecified Event(s)
1
10064 — 1 — —
Unit Hrs Exceeded 10080 — 1 — —
Comp 1 Hrs Exceeded 10081 — 1 — —
Network Failure 10091 — 1 — —
No Connection W/Unit 1 10092 — 1 — —
Unit(s) Disconnected 10093 — 1 — —
Unit Code Missing 10094 — — — —
Unit Code Mismatch 10095 — — — —
Low Memory 1 10097 — — — —
Ram / Battery Failure 10098 — — — —
(Parallel Flash) MEMORY 1 FAIL 10100 — — — —
(Serial Flash) MEMORY 2 FAIL 10101 — — — —
Front Door Open 10102 — — — —
Rear Door Open 10103 — — — —
Digital Scroll Compressor 1 Sensor Fail 10108 — — — —
Low Int Temperature 10110 — — — —
High Ext Dewpoint 10111 — — — —
Cabinet Temp Sensor Fail 10112 — — — —
Cabinet Humidity Sensor Fail 10113 — — — —
Ambient Temp Sensor Fail 10114 — — — —
Comp 1 Short Cycle 10132 — — — —
Reheat Lockout 10140 — — — —
Humidifier Lockout 10141 — — — —
Compressor(s) Lockout 10142 — — — —
Backup Ventilation 10143 — — — —
Door Open 10144 — — — —
Device Load 10146 — — — —
Alarm Status 10147 — — — —
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event.