BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 230
Compressors - Compressor 2
Compressor Hours Analog_Value 110 5267_1_2 RW Units: hr
1, 2, 3,
4, 5, 6
Compressor Hours Threshold Analog_Value 111 5268_1_2 RW Units: hr
1, 2, 3,
4, 5, 6
Dig Scroll Comp Discharge
Temp
Analog_Value 112 5353_1_2 RD Units: deg C
1, 2, 3,
4, 5, 6
Dig Scroll Comp Discharge
Temp
Analog_Value 10112
5353_1_2_deg
_F
RD Units: deg F
1, 2, 3,
4, 5, 6
Digital Scroll Compressor
Loading
Analog_Value 113 5619_1_2 RD Units: %
3, 4, 5,
6
Free Cooling / Chilled Water
Free Cooling Internal
Temperature Delta
Analog_Value 123 5356_1 RW Units: deg C
1, 2, 3,
4, 5, 6
Free Cooling Internal
Temperature Delta
Analog_Value 10123 5356_1_deg_F RW Units: deg F
1, 2, 3,
4, 5, 6
Free Cooling Fluid Temperature Analog_Value 124 5358_1 RD Units: deg C
1, 2, 3,
4, 5, 6
Free Cooling Fluid Temperature Analog_Value 10124 5358_1_deg_F RD Units: deg F
1, 2, 3,
4, 5, 6
Minimum Chilled Water Temp
Set Point
Analog_Value 125 5360_1 RW Units: deg C
1, 2, 3,
4, 5, 6
Minimum Chilled Water Temp
Set Point
Analog_Value 10125 5360_1_deg_F RW Units: deg F
1, 2, 3,
4, 5, 6
Free Cooling Valve Hours Analog_Value 126 5304_1 RW Units: hr
1, 2, 3,
4, 5, 6
Free Cooling Valve Hours
Threshold
Analog_Value 127 5305_1 RW Units: hr
1, 2, 3,
4, 5, 6
Chilled Water Valve Hours Analog_Value 128 5614_1 RW Units: hr
2, 3, 4,
5, 6
Reheat
Hot Water / Hot Gas Valve
Hours
Analog_Value 138 5363_1 RW Units: hr
1, 2, 3,
4, 5, 6
Hot Water / Hot Gas Valve
Hours Threshold
Analog_Value 139 5364_1 RW Units: hr
1, 2, 3,
4, 5, 6
Reheat - Electric Reheater 1
Electric Reheater Hours Analog_Value 150 5366_1_1 RW Units: hr
1, 2, 3,
4, 5, 6
Electric Reheater Hours
Threshold
Analog_Value 151 5367_1_1 RW Units: hr
1, 2, 3,
4, 5, 6
Reheat - Electric Reheater 2
Electric Reheater Hours Analog_Value 162 5366_1_2 RW Units: hr
1, 2, 3,
4, 5, 6
Electric Reheater Hours
Threshold
Analog_Value 163 5367_1_2 RW Units: hr
1, 2, 3,
4, 5, 6
Reheat - Electric Reheater 3
Electric Reheater Hours Analog_Value 174 5366_1_3 RW Units: hr
1, 2, 3,
4, 5, 6
Electric Reheater Hours
Threshold
Analog_Value 175 5367_1_3 RW Units: hr
1, 2, 3,
4, 5, 6
Table 78 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes