Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
39 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 11 Liebert CRV
- Status and Coil
Controller Liebert iCOM
®
v4
Data Label
Status Coil
Number
of Bits Scale Notes / Units
Supply Air Over Temperature 10001 1 Active on Alarm
Supply Air Under Temperature 10002 1 Active on Alarm
Return Air Over Temperature 10003 1 Active on Alarm
Supply Air Sensor Issue 10004 1 Active on Alarm
High Return Humidity 10005 1 Active on Alarm
Low Return Humidity 10006 1 Active on Alarm
Humidifier Hours Exceeded 10007 1 Active on Alarm
Dehumidifier Hours Exceeded 10008 1 Active on Alarm
Humidifier Under Current 10009 1 Active on Alarm
Humidifier Over Current 10010 1 Active on Alarm
Humidifier Low Water 10011 1 Active on Alarm
Humidifier Cylinder Worn 10012 1 Active on Alarm
Humidifier Issue 10013 1 Active on Alarm
Ext Humidifier Lockout 10014 1 Active on Alarm
Humidifier Control Board Not Detected 10015 1 Active on Alarm
Return Humidity Out Of Proportional Band 10016 1 Active on Alarm
Loss of Air Flow 10017 1 Active on Alarm
Fan Hours Exceeded 10018 1 Active on Alarm
Top Fan Issue 10019 1 Active on Alarm
Bottom Fan Issue 10020 1 Active on Alarm
Remote Sensor Issue Module Index 1 10021 1 Active on Alarm
Remote Sensor Issue Module Index 2 10022 1 Active on Alarm
Remote Sensor Issue Module Index 3 10023 1 Active on Alarm
Remote Sensor Issue Module Index 4 10024 1 Active on Alarm
Remote Sensor Issue Module Index 5 10025 1 Active on Alarm
Remote Sensor Issue Module Index 6 10026 1 Active on Alarm
Remote Sensor Issue Module Index 7 10027 1 Active on Alarm
Remote Sensor Issue Module Index 8 10028 1 Active on Alarm
Remote Sensor Issue Module Index 9 10029 1 Active on Alarm
Remote Sensor Issue Module Index 10 10030 1 Active on Alarm
Compressor 1 High Head Pressure 10031 1 Active on Alarm
Compressor 1 Low Suction Pressure 10032 1 Active on Alarm
Compressor 1 Hours Exceeded 10033 1 Active on Alarm
Dig Scroll Comp 1 Temp Sensor Issue 10034 1 Active on Alarm
Dig Scroll Comp 1 Over Temp 10035 1 Active on Alarm
Compressor 1 Low Pressure Transducer Issue 10036 1 Active on Alarm
Ext Compressor Lockout 10037 1 Active on Alarm
Compressor 1 Short Cycle 10038 1 Active on Alarm
Compressor 1 High Pressure Transducer Issue 10039 1 Active on Alarm
Compressor 1 Pump Down Issue 10040 1 Active on Alarm
Reheater Over Temperature 10041 1 Active on Alarm
Electric Reheater 1 Hours Exceeded 10042 1 Active on Alarm
Ext Reheat Lockout 10043 1 Active on Alarm
Condenser 1 Issue 10044 1 Active on Alarm
Condenser VFD Issue 10045 1 Active on Alarm
Condenser TVSS Issue 10046 1 Active on Alarm