Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
83 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 27 Liebert Challenger 3000
, Liebert Deluxe System/3
, Liebert Himod
, Liebert ICS
- Input and Holding - LAM
Controller Advanced Microprocessor - LAM
Liebert Products
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert Himod (LNA version - Using Liebert SiteScan
®
)
Liebert ICS
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Temperature 40001 1 -
Humidity 40002 1 -
Cooling 40003 1 1=On / 0=Off
Heating 40004 1 1=On / 0=Off
Humidification 40005 1 1=On / 0=Off
De-humidification 40006 1 1=On / 0=Off
Econ-O-Cycle 40007 1 1=On / 0=Off
Stages 40008 1 -
% Capacity 40009 1 -
Unit Status (On / Off) 40018 1 1=On / 0=Off (R/W)
Analog input 1 40023 1 A/D raw value w/ slope=1 and offset = 0
Analog input 2 40024 1 A/D raw value w/ slope=1 and offset = 0
Analog input 3 40025 1 A/D raw value w/ slope=1 and offset = 0
Analog input 4 40026 1 A/D raw value w/ slope=1 and offset = 0
Alarm Points
Discrete alarm objects available;
use autodiscover for this unit
Communications 40289 1 Bit 0
Local Off 40289 1 Bit 1
Remote Off 40289 1 Bit 2
High Head Pressure 1 40289 1 Bit 3
High Head Pressure 2 40289 1 Bit 4
Loss of Airflow 40289 1 Bit 5
Standby Glycol Unit On 40289 1 Bit 6
Liquid Detected 40289 1 Bit 7
Change Filters 40289 1 Bit 8
High Temperature 40289 1 Bit 9
Low Temperature 40289 1 Bit 10
High Humidity 40290 1 Bit 0
Low Humidity 40290 1 Bit 1
Humidifier Problem 40290 1 Bit 2
No Water in Humidifier Pan 40290 1 Bit 3
Compressor 1 Overload 40290 1 Bit 4
Compressor 2 Overload 40290 1 Bit 5
Main Fan Overload 40290 1 Bit 6
Manual Override 40290 1 Bit 7
Smoke Detected 40290 1 Bit 8
Loss of Water 40290 1 Bit 9
Standby Unit On 40290 1 Bit 10
Low Suction 40291 1 Bit 0
Short Cycle 40291 1 Bit 1
Loss of Power 40291 1 Bit 2