Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 148
Table 55 Liebert NXL
- 60Hz, UL version (Model 40) - Status and Coil
Data Label
Status Coil # of Bits Notes NXL Type
Battery Self Test 10082 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Low Shutdown 10092 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Shutdown - REPO 10093 1 Active on Alarm N+1, 1+N, 1+1, SMS
UPS Output on Bypass 10129 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Output Load on Maint. Bypass 10132 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Main Battery Disconnect Open 10136 1 Active on Alarm N+1, 1+N, 1+1, SMS
Bypass - Excess Auto Retransfers 10147 1 Active on Alarm SCC, 1+N, 1+1, SMS
Battery Low 10152 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Shutdown - EPO 10157 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Output Off 10158 1 Active on Alarm Deprecated
Battery Over Temperature 10172 1 Active on Alarm N+1, 1+N, 1+1, SMS
Inlet Air Over Temperature 10173 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Input Current Imbalance 10185 1 Active on Alarm N+1, 1+N, 1+1, SMS
System Input Phs Rotation Error 10191 1 Active on Alarm N+1, 1+N, 1+1, SMS
Rectifier Failure 10259 1 Active on Alarm N+1, 1+N, 1+1, SMS
Inverter Failure 10263 1 Active on Alarm N+1, 1+N, 1+1, SMS
Main Controller Fault 10293 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS
Bypass Not Available 10321 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Overload Phase A 10322 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Overload Phase B 10323 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Overload Phase C 10324 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Auto Retransfer Failed 10325 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Static Switch Unavailable 10326 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Static Switch Overload 10327 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Excessive Pulse Parallel 10328 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Auto Transfer Failed 10329 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Frequency Error 10330 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass - Manual Rexfr Inhibited 10331 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass - Manual Xfr Inhibited 10332 1 Active on Alarm SCC, 1+N, 1+1, SMS
Bypass Static Switch Off Extrnl 10333 1 Active on Alarm CE only
Battery Charging Reduced-Extrnl 10334 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Capacity Low 10335 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Discharging 10336 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Temperature Imbalance 10337 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Temperature Sensor Fault 10338 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Charging Inhibited 10339 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 1 Open 10340 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 2 Open 10341 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 3 Open 10342 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 4 Open 10343 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 5 Open 10344 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 6 Open 10345 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 7 Open 10346 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 8 Open 10347 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery - External Monitor 1 10348 1 Active on Alarm N+1, 1+N, 1+1, SMS
Battery - External Monitor 2 10349 1 Active on Alarm N+1, 1+N, 1+1, SMS