Emerson MODBUS 485 Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
21 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Condenser Issue - Event Control 1 30377 40377 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Condenser Issue - Event Control 2 30378 40378 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Condenser Issue - Event Type 1 30379 40379 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Condenser Issue - Event Type 2 30380 40380 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
System Event Acknowledge/Reset 40381 1
2 = Reset
4 = Acknowledge
1, 2, 3, 4, 5, 6
Air Temperature Control Sensor 30481 40481 1
0 = Supply
1 = Remote
2 = Return
2, 3, 4, 5, 6
Supply Air Over Temp Threshold 30482 40482 1 10 deg C 2, 3, 4, 5, 6
Supply Air Over Temp Threshold 30755 40755 1 10 deg F 2, 3, 4, 5, 6
Supply Air Under Temp Threshold 30483 40483 1 10 deg C 2, 3, 4, 5, 6
Supply Air Under Temp Threshold 30756 40756 1 10 deg F 2, 3, 4, 5, 6
Outside Air Temperature 30484 1 10 deg C 2, 3, 4, 5, 6
Outside Air Temperature 30757 1 10 deg F 2, 3, 4, 5, 6
Humidity Proportional Control Type 30485 40485 1
0 = Relative
1 = Compensated
2 = Predictive
3 = Dew Point
2, 3, 4, 5, 6
Ext Air Sensor A Dew Point Temp 30486 - 1 10 deg C 2, 3, 4, 5, 6
Ext Air Sensor A Dew Point Temp 30758 - 1 10 deg F 2, 3, 4, 5, 6
Ext Dew Point Over Temp Threshold 30487 40487 1 10 deg C 2, 3, 4, 5, 6
Ext Dew Point Over Temp Threshold 30759 40759 1 10 deg F 2, 3, 4, 5, 6
Ext Dew Point Under Temp Threshold 30488 40488 1 10 deg C 2, 3, 4, 5, 6
Ext Dew Point Under Temp Threshold 30760 40760 1 10 deg F 2, 3, 4, 5, 6
Compressor Lockout 30489 40489 1
0 = disabled
1 = enabled
2, 3, 4, 5, 6
Main Chilled Water Valve 30491 40491 1
0 = Valve 1
1 = Valve 2
2, 3, 4, 5, 6
Reheater Lockout 30492 40492 1
0 = disabled
1 = enabled
2, 3, 4, 5, 6
Humidifier Lockout 30493 40493 1
0 = disabled
1 = enabled
2, 3, 4, 5, 6
Fan Control Sensor 30494 40494 1
0 = Supply
1 = Remote
2 = Return
3 = Manual
2, 3, 4, 5, 6
Fan Speed Minimum Set Point 30495 40495 1 % 2, 3, 4, 5, 6
Fan Speed Temperature Set Point 30497 40497 1 10 deg C 2, 3, 4, 5, 6
Fan Speed Temperature Set Point 30761 40761 1 10 deg F 2, 3, 4, 5, 6
Standby Units 30498 40498 1 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes