E6581381
F-5
6
6.3 Terminal function selection
6.3.1 Keeping an input terminal function always active (ON)
H : Always-active function selection 1
H
: Always-active function selection 2
• Function
This parameter specifies an input terminal function that is always to be kept active (ON).
[Parameter setting]
Title Function Adjustment range Default setting
H
Always-active function selection 1
0-71 (
⇒ See page K-15)
0 (No function)
H
Always-active function selection 2
0-71 (
⇒ See page K-15)
1 (Standby)
* Coast stop
The standard default setting is for deceleration stop.
To make a coast stop, assign a "1(ST)" terminal
function to an idle terminal using the programmable
terminal function.
Change to
H
=
.
For coast stop, OFF the ST terminal when stopping
the motor in the state described at left.The monitor on
the inverter at this time will display
QHH
.
Motor
speed
ON
OFF
ON
OFF
F terminal
ST terminal
Coast stop
6.3.2 Modifying input terminal functions
H
: Input terminal selection 1 (F)
H
: Input terminal selection 2 (R)
H
: Input terminal selection 3 (RES)
H
: Input terminal selection 8 (VIA)