Toshiba VF-FS1 Power Supply User Manual


 
E6581381
K-13
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0851 Operation at
communication error
by disconnection
- - 0:Inverter stop, communication
command, frequency mode open
(by EOQF, HOQF)
1:None (continued operation)
2:Deceleration stop
3:Coast stop
4:Communication error (GTT trip)
or Network error (GTT trip)
46.21
H
0856
Number of motor
poles for
communication
- - 1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
2
H
0870
Block write data 1 - - 0
H
0871
Block write data 2 - -
0: No selection
1: Command 1
2: Command 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
6: Motor speed command
0
H
0875
Block read data 1 - - 0
H
0876
Block read data 2 - - 0
H
0877
Block read data 3 - - 0
H
0878
Block read data 4 - - 0
H
0879
Block read data 5 - -
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
11: Output motor speed monitor
0
H
0880
Free notes - 1/1 0-65535 0
H
0890
Parameter for
option 1
- 1/1 0-65535 0
H
0891
Parameter for
option 2
- 1/1 0-65535 0
6.22
H
0892
Parameter for
option 3
- 1/1 0-65535 0
H
0893
Parameter for
option 4
- 1/1 0-65535 0
H
0894
Parameter for
option 5
- 1/1 0-65535 0
H
0895
Parameter for
option 6
- 1/1 0-65535 0
H
0896
Parameter for
option 7
- 1/1 0-65535 0
H
0897
Parameter for
option 8
- 1/1 0-65535 0
H
0898
Parameter for
option 9
- 1/1 0-65535 0
H
0899
Parameter for
option 10
- 1/1 0-65535 0