E6581381
K-12
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0734
Prohibition of
panel emergency
stop operation
- - 0: Permitted
1: Prohibited
0 6.20.1
H
0735
Prohibition of
panel reset
operation
- - 0: Permitted
1: Prohibited
0
H
0738
Head of
parameter display
selection
--0: AUF
1: AUH
0 6.20.7
H
0748
Integral output
power retention
selection
- - 0: Disabled
1: Enabled
1 6.20.8
H
0749
Display unit
selection for
integral output
power
- - 0: 1=1kWh
1: 0.1=1kWh
2: 0.01=1kWh
3: 0.001=1kWh
*1
*1 : Default values vary depending on the capacity. ⇒ See the table of page K-14.
• Communication parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0800
Communication
rate
- - 0: 9600bps
1: 19200bps
1
H
0801
Parity - - 0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
1
H
0802
Inverter number - 1/1 0-247 0
H
0803
Communication
error trip time
s 1/1 0: Disabled
1-100
0
H
0805
Communication
waiting time
s 0.01/0.01 0.00: Regular communication
0.01-2.00
0.00
H
0806
Setting of master
and slave for
communication
between inverters
- - 0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in case
the master inverter fails)
2: Slave (Emergency stop tripping in
case the master inverter fails)
3: Master (transmission of frequency
commands)
4: Master (transmission of output
frequency signals)
0
6.21
H
0811
Communication
command point 1
setting
% 1/1 0-100 0
H
0812
Communication
command point 1
frequency
Hz 0.1/0.01 0.0-200.0 0.0
H
0813
Communication
command point 2
setting
% 1/1 0-100 100
H
0814
Communication
command point 2
frequency
Hz 0.1/0.01 0.0-200.0 50.0 (WP)
60.0 (WN)
6.5.2
6.21
H
0829
Selection of
communication
protocol
- - 0: Toshiba inverter protocol
1: ModbusRTU protocol
2: Metasys N2 protocol
3: APOGEE FLN protocol
4: BAC-net protocol
06.21