Toshiba VF-FS1 Power Supply User Manual


 
E6581381
C-7
3
Remote mode selection,
Operation frequency setting, running and stopping using external
signals.
(1) Wiring
(2) Parameter setting
Title Function Setting value
EOQF
Command mode selection 0
HOQF
Frequency setting mode selection 1 1or2
(3) Operation
Run/stop: ON/OFF input to F-CC, R-CC. (Set SW4 to Sink logic)
Frequency setting: VIA and VIB: 0-10Vdc (External potentiometer)
VIA: Input 4-20mAdc.
Use the VIA (SW3) slide switch to switch between voltage and current to the VIA terminal.
Voltage input: V side
Current input: I side
+Please turn off the lamp by pressing the key when the LOC/REM key lamp is lit.
Control
circuit
Motor
IM
F
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Run forward signal
R
PC/-
PA/+
Power circuit
Run backward signal
MCCB
CC
Common
CC
VIB
VIA PP
Voltage signal: 0
10V, Current signal: 4
20mA
External potentiometer
(Otherwise, input voltage signal (0~10V) between the terminals VIA-CC.)
Noise
filter
*
Ex.2
LOC
REM