5. Basic parameters
Before you operate the inverter, the parameters that you must first program are the basic parameters.
5.1 Setting acceleration/deceleration time
CW Automatic acceleration/deceleration
CEE
Acceleration time 1
FGE
Deceleration time 1
Function
1) For acceleration time 1 CEE programs the time that it takes for the inverter output frequency to go from
0Hz to maximum frequency HJ.
2) For deceleration time 1 FGE programs the time that it takes for the inverter output frequency to got
from maximum frequency HJ to 0Hz.
5.1.1 Automatic acceleration/deceleration
This automatically adjusts acceleration and deceleration time in line with load size.
CW =
* Adjusts the acceleration/deceleration time automatically within the range of 1/8 to 8 times as long as the
time set with the CEE or FGE, depending on the current rating of the inverter.
CW =
* Automatically adjusts speed during acceleration only. During deceleration, speed is not adjusted
automatically but reduced at the rate set with FGE.
Output
frequency (Hz)
Deceleration
time
Acceleration
time
HJ
When load is small
Time
[sec]
0
Shorten acceleration/deceleration time
Deceleration
time
Acceleration
time
HJ
When load is large
Output
frequency (Hz)
Time
[sec]
0
Lengthen acceleration/deceleration time
Set CW (automatic acceleration/deceleration) to or .